Home Fault finding Gas safety check: the checklist
Fault finding
Gas safety check: the checklist
A memory jogger for each appliance, in the order you'd do it. The standards and the manufacturer's instructions are the procedure.
Before you start
- Who's responsible for the property, and which appliances are on the record
- Safe to touch: non-contact detector over each appliance and the pipework (chapter 1)
- Meter and emergency control valve: accessible, handle works, labelled
- Main equipotential bond: on the customer’s side of the meter, before any branch, within 600 mm of the meter outlet where practicable
The installation
- Tightness test to IGEM/UP/1B Edition 4: let-by, then the test, with the allowed drop from the installation volume (8.2, page 24)
- Pipework: supported, sleeved through walls, no damage or corrosion
- Working pressure at the meter, the biggest appliance on full and the rest at half. Natural gas: 18.5 to 23 mbar (19 to 23 is the figure for meter work). Outside that, call the gas emergency service. Standing no more than 30 mbar
- Drop from the meter to the appliance: no more than 1 mbar
Each appliance
- Suitable for the room it's in. Stable and secure. Case and seals intact on a room-sealed appliance
- Ventilation as the appliance needs. Nothing blocking a vent
- Working or burner pressure against the data plate, or the gas rate against the manufacturer's heat input
- Flame picture right for the burner
- Safety devices work: flame supervision, overheat, and any air or pressure switch
Flues and combustion
- The whole flue you can see: joints, supports, the terminal and its clearances, a guard where it's needed
- Flue in a void: hatches at least 300 mm square, no joint more than 1.5 m from one, and a CO alarm. Can't inspect it: At Risk
- Open flue: flue flow test, then a spillage test with the appliance running
- Analyser: flue integrity at the air inlet test point, O2 at least 20.6%
- Combustion: CO and CO/CO2 ratio against the manufacturer's figures, which run from 0.002 to 0.004 for condensing boilers. With no manufacturer figure: under 0.004 with an air/gas ratio valve, 0.008 without
CO alarms and the record
- In England, in a rented home: a CO alarm in every room used as living accommodation that has a fixed combustion appliance, other than a gas cooker. Anywhere in the UK, a new or replacement fixed appliance needs an alarm in its room. Tested
- Record each appliance: where it is, what you checked, what you found, what you did
- Landlord record: valid 12 months, can be done up to 2 months early keeping the same due date. The landlord keeps each record until two further checks have been made
- A safety check is not a service. Say so on the paperwork
Stop.
When it's unsafe. Follow IGEM/G/11. Immediately Dangerous: with consent, disconnect it and cap it. If they refuse, turn it off if you can and ring the gas emergency number. At Risk: with consent, turn it off at its gas valve, or pull its fuse if you can't. Turning the stat down doesn't count. Label it, give the responsible person the warning notice, and report it where the rules say so.