Home Fault finding S plan wiring diagram

Fault finding

S plan wiring diagram

Each zone has its own two-port valve, and either valve, once fully open, fires the boiler and pump. Here is how the lives run and where every cable lands.

S plan: two zone valves

Each zone has its own two-port valve. Either valve, once open, fires the boiler and pump.

S plan, how the lives run. Programmer heating on feeds the room stat; when it calls, it puts the heating zone valve brown wire live. Programmer hot water on feeds the cylinder stat; when it calls, it puts the hot water zone valve brown wire live. Each valve has a permanent live on grey to its end switch, and its orange goes live to the boiler and pump once the valve is fully open. Blue is the motor neutral.

How it works: the lives only. Page 21 shows it wired at a wiring centre. The greys share a permanent live. Each orange goes live only when its valve is fully open. Some two-port valves have a white wire that S plan doesn't use: it is cut back and made safe.

Which wire does what

BrownMotor live, from the room stat or cylinder stat when it calls.
BlueMotor neutral.
GreyPermanent live to the end switch.
OrangeSwitched live out to boiler and pump, once the valve is fully open.
Green/yellowEarth.

The sequence

Stat calls, brown goes live, the motor drives the valve open against its spring. At fully open a cam makes the end switch, grey to orange, and the boiler and pump start. Stat satisfied: brown drops, the spring shuts the valve and orange goes dead.

With both zones shut the pump has nowhere to go. An S plan needs an automatic bypass valve, unless the boiler has a bypass of its own.

Fault finding

  1. Live Stat calling, no heat in that zone. AC volts brown to N at the valve: about 230 V? None: the stat, the programmer or the wiring.
  2. Live Brown live, motor not turning. Check the blue to the neutral bar has about 230 V across it too. Brown live and blue good with no movement: the motor has failed.
  3. Live Valve open, orange dead. First check the grey is live at the valve. Grey live, orange dead with the valve fully open: the end switch. A new head.
  4. Lever across by hand. On many valves this makes the end switch and the boiler fires. Some spring back, some stay put, so it varies by valve. Fires: the motor is faulty, the valve body is fine.
  5. Synchron motor. Isolated, brown lifted, ohms brown to N: typically 2,000 to 2,500 Ω, or the manufacturer’s figure for that motor. OL or far out is faulty.

Boiler runs when nothing calls

A valve stuck open keeps its orange live. Isolate, take each valve's orange off at the wiring centre in turn and power up. The one that stops it is the one stuck open.

A low reading, tens of volts, on a wire that should be dead is usually backfeed through a control. Look for a full 230 V before you call a wire live.

S plan at the wiring centre

Two zone valves, one wiring centre. Each valve’s orange lands on the same switched live, so either one fires the boiler.

Example: terminal numbers vary by wiring centre, follow the label in the box.

S plan wired through a 10-way wiring centre. Terminal 1 live, 2 neutral, 3 earth from the 3 amp fused spur. Programmer heating on to 4, which feeds room stat 1; room stat 3 to 5, which feeds the heating zone valve brown. Programmer hot water on to 6, which feeds cylinder stat common; cylinder stat 1 to 7, which feeds the hot water zone valve brown. Both valve greys on the permanent live, terminal 1. Both oranges, the boiler switched live and the pump live on 8. Neutrals on 2, earths on 3.

Every cable to the wiring centre. The same circuit as page 20, wired the way you’ll find it. Both greys share the permanent live on 1.

What lands where

1 LFused spur live, programmer L, both valve greys, boiler permanent live.
2 NSpur, programmer, room stat 2 (if it has one), both valve blues, pump, boiler.
3 ESpur, both valve green/yellows, pump, boiler.
4Programmer CH ON (4) to room stat 1.
5Room stat 3 to the heating valve brown.
6Programmer HW ON (3) to cylinder stat C.
7Cylinder stat 1 to the hot water valve brown.
8Both valve oranges, boiler switched live, pump live.

On the job

Read the box first. Use the label inside the lid, or trace each cable back to its control.

Which valve keeps the boiler on? Isolated, lift one orange off 8, power up and watch. Then the other.

A white core on the valve? Some two-port valves have one. S plan doesn’t use it: cut it back and make it safe.

Two-wire and battery room stats have no neutral. Leave terminal 2 at the stat unused and follow the stat’s own instructions for its two terminals.

Cylinder stat needs C and 1 only. Terminal 2 isn’t used on an S plan.

Boiler wiring varies. Follow the boiler’s manual for its own terminals and any pump overrun.

Free guide

Get Fault Finding Basics as a PDF

This lesson is part of Fault Finding Basics, our free 26-page guide: safe isolation, your meter, how a combi works and the five tests that find most faults. Add your email and it comes straight over.

Send me the guide

Want every test? The Flint Field Guide has all 56 chapters with a video for every test. £97 once, updates included.

All fault finding lessons

For competent, Gas Safe registered engineers. Isolate and prove dead before any electrical test. Always work to the manufacturer's instructions and the current standards, and check every figure against the appliance data badge and manual.