Boiler not igniting or locking out once lit? Test the spark, the electrode gap and the flame current, and tell an ignition fault from a flame sensing fault.
What it does
The spark lights the gas. Then the PCB has to see the flame or it shuts the gas off. It puts a voltage on the sense electrode, and a flame conducts a tiny DC current from the electrode to the burner, which is earthed. It's measured in microamps. Some boilers use one electrode for both jobs.
Symptoms when it fails
- No spark: fan runs, then it locks out
- Sparks, gas on, no flame
- Lights for a few seconds, then locks out: flame not proved
- Keeps sparking with the flame lit
How to test it
- Read the flame signal in the service menu if the boiler has one. No leads needed.
- Isolate power and gas. Lock off and prove dead (chapter 1).
- Look at the electrodes. Cracked ceramic, worn or corroded tips, carbon, a wrong gap, a damaged lead or cap.
- Check the gap against the manufacturer's figure. Set it with the electrode out, never by bending it in place.
- No spark: continuity of the lead and electrode, then the ignition unit's supply. On many boilers the spark comes from the PCB.
- Sparks with gas on but won't light: suspect the gas supply or the gas valve (4.4).
- Live Flame current. Meter on µA DC in series in the sense lead, only where the manufacturer allows it. Red lead in the µA socket, and back afterwards.
- Live Prove the flame sensing. Burner lit, turn the gas off at the appliance valve. Pass: it locks out within 60 seconds, or within 2 minutes of relight tries, and doesn’t relight when the gas is back. One that keeps sparking and lights normally once the gas is back also passes. Wait 2 minutes before you open the valve, then reset and watch it light.

The spark jumps the gap. The flame then carries a tiny DC current from the sense electrode to the earthed burner, and back to the PCB.
Typical readings
Gaps and minimums vary by model. Set to the figure for the boiler in front of you.
| Electrode gap | |
|---|---|
| 3 to 5 mm | The usual spark gap. |
| Flame current · µA DC · burner lit | |
| 5 to 30 µA | Usual for a good flame. |
| Under the minimum | The minimum is often 1 to 1.5 µA. Electrode, then earth. |
| Service menu flame value | |
| Varies | Often display units, not µA. Read it against the boiler’s own table. |

Illustration. Out of the burner: the spark pair (left) and its gap, and the flame sense electrode (right).
Common failures
Cracked ceramic. The spark tracks to earth inside the boiler instead of across the gap.
Worn, bent or coated tip. Weak spark, low flame current.
Lead or cap damaged. Damp or cracked. Sparks to the case.
Poor burner earth. Low flame current with a good flame.
Live and neutral swapped. Some boilers can’t prove the flame. Others run as normal. Check polarity (chapter 2).