Home Fault finding How to test a boiler circulating pump
Fault finding
How to test a boiler circulating pump
Boiler pump not working? Test the supply, the winding and the shaft in order, so you know whether it is the pump, the board or something stopping the flow.
What it does
The pump moves water through the heat exchanger and round the system. If it stops, the boiler overheats and locks out.
Most boiler pumps fitted since 2015 are electronic: a permanent-magnet motor run by electronics in the head. The ErP energy rules brought them in for separate pumps from 2013 and for pumps built into boilers from August 2015. They test differently from the older standard pumps.
Symptoms when it fails
- Burner fires, then the overheat stat trips or it locks out
- Radiators stay cold while the boiler is running
- Pump is silent, or hums but nothing moves
- Pump only runs flat out, whatever the boiler asks for
- The 3 A fuse keeps blowing
How to test it
- Safely isolate the boiler. Switch off, pull the fuse, prove dead and lock off (chapter 1). Take the case off.
- Standard or electronic? Speed switch and one lead: standard. Status light or a thin second lead: electronic.
- Live Check the supply. Power back on, heating calling. AC volts on the supply lead, black on N first. Expect about 230 V. Mains is live. Leads and probes to GS38, touch nothing else.
- Electronic Read the status light. Green: running. Red or flashing: an alarm. Codes vary, so check the label.
- Live Electronic Check the signal. DC volts across the signal wires: a few volts that change as the boiler changes pump speed.
- Isolate again. Lock off and prove dead.
- Standard Test the windings. Lead off, ohms, L to N. Never on an electronic pump: the reading tells you nothing.
- Check the rotor is free. Cloth under, screw out, turn the shaft. Electronic pump with no screw: take the head off.
- Refit and test. Call for heat, check the radiators warm. Electronic pump with supply, no alarm, a signal and a free rotor but still not pumping: replace the head.
Many electronic pumps also have a thin signal lead from the PCB. Some have a centre screw (dotted).
Typical readings
Figures vary by model. Go by the pump’s own data.
| Supply L to N · heating calling | |
|---|---|
| About 230 V | Power is reaching the pump. |
| 0 V | No call for heat, or a PCB fault. |
| Status light Electronic | |
| Steady green | Running. |
| Red or flashing | Alarm: blocked rotor, low supply voltage or an electrical fault. |
| Signal wires · DC volts Electronic | |
| A few volts | Changes with speed. OK. |
| No signal | Runs flat out. Lead, then PCB. |
| Windings L to N · lead off Standard | |
| 120 to 250 Ω | Normal. |
| Under 100 Ω | Burnt windings. Replace. |
| OL | Open circuit. Replace. |
| Rotor · screw out | |
| Turns freely | Rotor OK. |
| Stiff or stuck | Seized. Free it, or replace. |
| Water keeps coming | Worn bearings. Replace. |
DC volts shows an average. For the exact duty cycle you need a meter with a duty-cycle setting, or a scope.
Common failures
Seized rotor. Sludge or debris. Hums, or silent.
Signal lost. Runs flat out. Often the lead or PCB.
Windings or capacitor. Standard pumps. Won't start.
Air lock. Gurgling or rattling. Bleed system and pump.
Worn bearings. Water keeps coming from the vent screw.
Weak pump. Kettling, overheat trips, relief valve lifting.
Free guide
Get Fault Finding Basics as a PDF
This lesson is part of Fault Finding Basics, our free 26-page guide: safe isolation, your meter, how a combi works and the five tests that find most faults. Add your email and it comes straight over.
Send me the guideWant every test? The Flint Field Guide has all 56 chapters with a video for every test. £97 once, updates included.
For competent, Gas Safe registered engineers. Isolate and prove dead before any electrical test. Always work to the manufacturer's instructions and the current standards, and check every figure against the appliance data badge and manual.