Home Fault finding How to use a multimeter on a boiler

Fault finding

How to use a multimeter on a boiler

Which setting for which test, and how not to blow it. Typical values are a guide: the manufacturer's data for the boiler in front of you always wins.

Your multimeter

What it's for

On a breakdown the meter answers two questions: is power reaching the part (AC volts), and is the part itself whole (ohms or continuity). Most faults are found with those two settings. DC volts and microamps come out for sensors, signal leads and flame current.

What it's not for

Stop.

Proving dead. Use a two-pole voltage indicator to GS38 and a proving unit. Prove the tester on the proving unit, test L-N, L-E and N-E, then prove the tester again.

A multimeter on the wrong setting, or with its fuse blown, shows 0 V on a live circuit. Some older manuals tell you to prove dead with the meter on AC volts. Gas Safe TB 118A says not to, because of that false 0 V.

Run a non-contact detector over the case before you put a hand on it.

Set it up before you touch anything

  1. Check the leads. Test leads and probes must meet GS38: fused, finger guards, no more than 4 mm of bare tip, no cracks in the insulation.
  2. Black into COM, red into V Ω. The current sockets are only for measuring current.
  3. Probes together. Continuity should beep and ohms should read close to zero. Note what the leads read and take it off low readings.
  4. Pick the setting first, then probe. Never turn the dial with the probes on a live circuit: on the way round it can pass a current range and short the probes.
  5. Live Black on first, red on last. Black goes on N or E, then red on L. Take red off first.

Use a meter rated CAT III 600 V or better for work at the fused spur. An auto-ranging meter picks its own range. On a manual one, start on the range above what you expect: above 250 V for mains.

Digital multimeter set up for a live voltage test: display reads 230.4 volts AC, dial on AC volts, black lead in COM, red lead in the volts and ohms socket, both current sockets empty.

Set up for a live voltage test. Red in V Ω, black in COM, dial on AC volts. The current sockets stay empty unless you are measuring current.

Reading the display

On ohms or continuity
OLOpen circuit, or more than the range can show.
0.00A closed contact, a link or a short.
Won't settlePoor probe contact, or the part is still plugged in.
On volts
OLOver the range. Go up a range.
0.00No voltage on that setting. Not proof of dead.
Minus signDC with the leads the other way round. The number is still good.
Won't settleA loose connection, or a signal that changes, like a PWM speed signal.

Which setting for which test

Typical values. The manufacturer's data for the boiler in front of you always wins.

TestSettingPowerWhere to probeWhat good looks like
Electrical checks at the supply
Supply reaching a partV ACLive callingL and N at the part's plugAbout 230 to 240 V
PolarityV ACLive no demandL-N, L-E, N-E at the terminal stripSee the triangle below
Earth continuityΩOff, fuse outEarth screw at the spur to the boiler case1 Ω or less, after taking off the leads
Short circuitΩOff, fuse out, boiler switch onL and N at the terminal stripNear zero is a short. A figure may be the PCB: check the manual
Resistance to earthΩ top rangeOff, fuse out, switches and stats onL to E, then N to EOL. A low reading is a fault; megohms can be the electronics: check the manufacturer’s floor
Parts, with the boiler isolated
NTC thermistorΩOff, sensor unpluggedAcross the two pinsMatches the sensor’s table at the pipe temperature. 10 or 12 kΩ at 25 °C is common
Fan windings , mains fanΩOff, wires offL and N on the fan30 to 100 Ω is normal for most mains fans. Near zero is burnt, OL is open
Pump windings , standard pump onlyΩOff, lead offL and N on the pumpTypically 120 to 250 Ω. Near zero is burnt, OL is open
Gas valve coilΩOff, plug offAcross each coilTens of Ω to several kΩ, by valve. Near zero or OL is faulty
Zone valve motorΩOff, motor wire liftedMotor wire to NTypically about 2,000 to 2,500 Ω
Switches: APS, microswitch, flow switch, overheat statContinuityOff, plug offCOM to NO, then COM to NCClosed beeps, near 0 Ω. Open reads OL. Check it changes over
FuseContinuityOut of the holderEnd to endBeeps
Signals, with the boiler running
Electronic pump or fan signalV DCLive callingAcross the signal wiresA few volts that change as the speed changes
Flame currentµA DCLive burner litMeter in series in the flame sense lead, where the manufacturer allows itUsually 5 to 30 µA. The minimum varies by model

Many boilers show flame current and sensor temperatures in a service menu. Use that first: it means no leads in the flame circuit.

Polarity check. Three terminals: live, neutral and earth. Live to neutral about 230 volts, live to earth about 230 volts, neutral to earth 0 to 15 volts.

Polarity: what the three readings tell you

L-NL-EN-E
Correct2302300 to 15
L and N swapped2300 to 15230
Neutral lost0 to 15230230

Volts AC, power on, no demand. N to E up to about 15 V is normal, though some boilers want under 10 V. Over 15 V from N to E points to the house wiring: check polarity at the spur, then it's a job for an electrician.

Three ways to put the meter on

Three circuits. Volts: meter across the part with the power on. Ohms: supply unplugged, meter across the part on its own. Current: the flame sense lead broken and the meter put in the gap, between the PCB and the flame electrode, reading microamps DC.

Volts: across the part, power on. Ohms: power off and the part unplugged, or you measure the PCB as well. Current: break the circuit and put the meter in the gap, with the red lead moved to the µA socket. Move it back afterwards.

How not to blow it

Red lead left in a current socket. Measuring mains like that puts a short through the meter. At best it blows the meter's fuse. Put the red lead back in V Ω after every current reading.

Ohms on a live circuit. The reading means nothing and it can kill the meter. Isolate first.

Turning the dial with the probes on. Lift the probes, change the setting, then probe again.

A part still plugged in. The meter reads through the PCB and the loom as well. Unplug the part at its own plug.

A thermistor reading with no temperature. On the example sensor on page 11, 4.7 kΩ is right at 50 °C and wrong at 20 °C. Take the pipe temperature first.

What the meter can't tell you

Winding resistance on an electronic pump. The head holds electronics, not a plain winding, so the figure means nothing. Check the supply, the status light and the signal instead.

A true insulation figure. Resistance to earth on the ohms range only finds a hard fault. An insulation resistance tester puts a test voltage on the circuit and finds the leaky ones.

Whether a motor can turn. A zone valve motor or a pump can read fine on ohms and still be seized. Look at it and turn it.

That 0 V means dead. A meter on the wrong setting shows 0 V on a live circuit. Prove dead with the right tester.

Worked example: a mains fan that won't start

  1. Live Heating calling, V AC at the fan plug, L to N. 0 V: the fan isn't being asked. Check the PCB output and its fuse before you blame the fan.
  2. About 230 V and the fan sits still. Isolate, prove dead and lock off.
  3. Spin the impeller by hand. Stiff or rubbing points to the bearings, or the rotor catching the case.
  4. Spins freely: wires off, ohms across L and N. Near zero or OL against the manufacturer’s figure: the windings have gone. Replace the fan.
  5. Windings fine but it won't run on 230 V. Check the plug and terminals, then any speed resistor in the circuit.

Most modern fans run on low-voltage DC with a speed signal: DC volts, and the manufacturer's figures in Flint.

Free guide

Get Fault Finding Basics as a PDF

This lesson is part of Fault Finding Basics, our free 26-page guide: safe isolation, your meter, how a combi works and the five tests that find most faults. Add your email and it comes straight over.

Send me the guide

Want every test? The Flint Field Guide has all 56 chapters with a video for every test. £97 once, updates included.

All fault finding lessons

For competent, Gas Safe registered engineers. Isolate and prove dead before any electrical test. Always work to the manufacturer's instructions and the current standards, and check every figure against the appliance data badge and manual.