Service mode › Alpha

Alpha boiler service mode

How to put an Alpha boiler into service mode, so it holds maximum or minimum rate while you take combustion readings. 35 models from 18 Alpha installation and servicing manuals, each step with the page it came from.

Grouped by manual: one manual usually covers a range of outputs. The CO₂ figures are the manual's own. Set and check them with a calibrated analyser, never by eye.

Alpha C23/27 Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boilers

Covers: C27

GC 47-532-22, 47-532-23

Service Gas Pressure Check

  1. Turn the boiler off.
  2. Loosen the burner pressure test point screw on the gas valve.
  3. Connect a pressure gauge.
  4. Set selector switch to (DHW only) and fully open a hot water tap.
  5. Allow to run for 10 minutes to check pressures.
  6. After checks, disconnect gauge and tighten test point screw.

From manual 1.019966, page 16.

The burner pressure settings have been factory set and do not require adjusting. If incorrect, check that the inlet gas pressure is 20 mbar. (page 16)

Alpha CB50

Covers: CB50

GC 47-532-18

Entering Service/Test Mode

  1. Set the selector switch to 0.
  2. Loosen the burner pressure test point screw on the gas valve and connect a pressure gauge.
  3. To test Hot Water mode: Set selector to DHW icon and DHW thermostat to max.
  4. To test Central Heating mode: Set selector to DHW+CH icon and CH thermostat to max.

From manual 1.017833, page 18.

Exiting Service Mode

  1. Set the selector switch to 0 to turn off the boiler.
  2. Disconnect the pressure gauge and tighten the test point screw.
  3. Test for gas soundness using suitable leak detection fluid.

From manual 1.017833, page 20.

The burner pressure settings have been factory set and do not require adjusting. If incorrect, check that the inlet gas pressure is 20 mbar. (page 18)

Alpha CD50S and 70S

Covers: Cd50s Cd70s

Entering Installer Parameters

  1. Press the MODE and STEP keys at the same time for 2 seconds; the display will show the wording CODE.
  2. Change the value by operating the + or - keys until reaching the correct code.
  3. Press the STORE key to confirm.

From manual 1.027175, page 21.

GasCO₂ max rateCO₂ min rateCO max
LPG10.6% ± 0.2%10.1% ± 0.2%250 ppm

CO₂ and CO from manual 1.027175, page 4. Check against the data badge.

Warning: Before servicing the boiler, isolate the electrical supply and close the boiler gas service cock. The factory-set valve/adjustment is at P1 and Off-set adjustment screw (Fig. 23) (page 19)

Alpha E-Tec 28 and 33 Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boiler

Covers: E-Tec 33

GC 47-532-70

Chimney Sweep Mode (Service / Test Mode)

  1. Without any CH or DHW demand, press and hold the reset button for eight seconds and the boiler will fire at a fixed output.
  2. The parasol and snowman symbols will flash at the same time to indicate this mode.
  3. Using the DHW up and down buttons you can change between three predefined output levels: 0% (low fire), 80 - 90% (Max CH output), 99% (Max DHW output).
  4. This mode will remain active for fifteen minutes or can be cancelled by turning the boiler off.

From manual 1.042188 rev. ST.003781.001, page 29.

GasCO₂ max rateCO₂ min rateCO max
LPG11.2% (+0.2 / -0.4)10.0% (+0.4 / -0.2)–

CO₂ and CO from manual 1.042188 rev. ST.003781.001, page 5. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. If adjustment is recommended or required the engineer must be competent to carry out this work. (page 29)

Alpha E-Tec Plus 28, 33 and 38

Covers: E-Tec Plus 28, E-Tec Plus 33, E-Tec Plus 38

GC 47-532-77, 47-532-78, 47-532-79

Chimney Sweep Mode (Force Max / Min Rate)

  1. Without any CH or DHW demand, press and hold the reset button for eight seconds and the boiler will fire at a fixed output.
  2. The parasol and snowman symbols will flash at the same time to indicate this mode.
  3. Using the DHW up and down buttons you can change between three predefined output levels: 0% (low fire), 80-90% (Max CH output), and 99% (Max DHW output).
  4. This mode will remain active for fifteen minutes or can be cancelled by turning the boiler off.

From manual Part No. 1.043044 rev. ST.004614/001, page 31.

GasCO₂ max rateCO₂ min rateCO max
LPG11.4% (+0.1 / -0.3)10.6% (+0.3 / -0.1)–

CO₂ and CO from manual Part No. 1.043044 rev. ST.004614/001, page 6. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. If adjustment is recommended or required the engineer must be competent to carry out this work. (page 31)

Alpha E-Tec Plus 28NX, 33NX and 38NX

Covers: E-Tec Plus 28NX, E-Tec Plus 33NX, E-Tec Plus 38NX

GC 47-532-89, 47-532-90, 47-532-91

Chimney Sweep Mode (Combustion Check)

  1. Without any CH or DHW demand, press and hold the reset button for five seconds and the boiler will fire at a fixed output.
  2. Sc will be shown on the display (DHW digits) to indicate this mode.
  3. Once activated, select whether to make the check in CH status or DHW status by opening any hot water tap.
  4. If active in CH mode, the CH +/- buttons can be used to select the power from minimum power (0%) to maximum CH power (99%) in 1% intervals.
  5. If active in DHW mode the CH +/- buttons can be used to select the power from minimum power (0%) to maximum DHW power (99%) in 1% intervals.
  6. This mode will remain active for fifteen minutes or can be cancelled by pressing the RESET button.

From manual 1.048200, page 36.

GasCO₂ max rateCO₂ min rateCO max
LPG10.2% (-10.4)9.7% (-9.9)–

CO₂ and CO from manual 1.048200, page 7. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. (page 36)

Alpha Evoke 28 and 33

Covers: Evoke

GC 37-532-76, 47-532-71, 47-532-72, 47-532-75

Entering Chimney Sweep Mode

  1. Ensure no CH or DHW demand.
  2. Press and hold the reset button for eight seconds.
  3. Boiler will fire at a fixed output (display flashes parasol and snowman).
  4. Use DHW up/down buttons to toggle between 0%, 80-90% (Max CH), and 99% (Max DHW) outputs.

From manual 1.042372 rev. ST.003782.000, page 29.

GasCO₂ max rateCO₂ min rateCO max
Natural gas9.7% (+0.5 / -0.2)8.8% (+0.2 / -0.3)450 ppm
LPG11.4% (+0.1 / -0.3)10.6% (+0.3 / -0.1)–

CO₂ and CO from manual 1.042372 rev. ST.003782.000, page 5. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. If adjustment is recommended or required the engineer must be competent to carry out this work. (page 29)

Alpha Evoke 28NX and 33NX

Covers: Evoke 28NX, Evoke 33NX

GC 47-532-84, 47-532-85, 47-532-86, 47-532-87

Chimney Sweep Mode (Combustion Testing)

  1. Without any CH or DHW demand, press and hold the reset button for eight seconds and the boiler will fire at a fixed output.
  2. The parasol and snowman symbols will flash at the same time to indicate this mode.
  3. Using the DHW up and down buttons you can change between three predefined output levels: 0% (low fire), 80 - 90% (Max CH output), and 99% (Max DHW output).
  4. This mode will remain active for fifteen minutes or can be cancelled by turning the boiler off.

From manual 1.046746, page 30.

GasCO₂ max rateCO₂ min rateCO max
Natural gas9.2% ± 0.38.5% ± 0.2250 ppm
LPG10.2% ± 0.29.7% ± 0.2250 ppm

CO₂ and CO from manual 1.046746, page 5. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. If adjustment is recommended or required the engineer must be competent to carry out this work. (page 30)

Alpha InTec 12S, 18S, 28S Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing System Boilers

Covers: Intec 12S, Intec 18S, Intec 28S

GC 41-532-22, 41-532-23, 41-532-24, 41-532-25, 41-532-26, 41-532-27

Force Maximum Rate (Burner Pressure & Combustion Check)

  1. Press and hold in the reset button for eight seconds and the boiler will fire at a fixed output depending on the position of the boiler central heating thermostat knob.
  2. Turn the boiler central heating thermostat to maximum to check the maximum central heating burner pressure.
  3. With the boiler central heating thermostat set to maximum fully open a hot tap to check the maximum domestic hot water burner pressure.

From manual 1.030769, page 26.

ModelGasCO₂ max rateCO₂ min rateCO max
Intec 12SNatural gas9.4% ± 0.25%8.9%200 ppm
Intec 12SLPG10.8% ± 0.5%10.4%–
Intec 18SNatural gas9.4% ± 0.25%8.6% ± 0.25%200 ppm
Intec 18SLPG10.5% ± 0.5%9.7% ± 0.5%–
Intec 28SNatural gas9.5% ± 0.25%8.7% ± 0.25%200 ppm
Intec 28SLPG10.5% ± 0.5%9.7% ± 0.5%–

CO₂ and CO from manual 1.030769, page 4, 5. Check against the data badge.

Note: The burner pressure settings have been factory set and should not require adjusting. (page 26)

Alpha InTec 30GS and 40GS

Covers: Intec 30GS, Intec 40GS

GC 47-532-50, 47-532-51, 47-532-57, 47-532-58

Force fixed output / test burner pressures and combustion

  1. Press and hold in the reset button for eight seconds and the boiler will fire at a fixed output depending on the position of the boiler central heating thermostat knob.
  2. Turn the boiler central heating thermostat to maximum to check the maximum central heating burner pressure.
  3. With the boiler central heating thermostat set to maximum fully open a hot tap to check the maximum domestic hot water burner pressure.

From manual 1.038435 ST.001940/000, page 27.

ModelGasCO₂ max rateCO₂ min rateCO max
Intec 30GSNatural gas9.4% ± 0.25%8.6%200 ppm
Intec 30GSLPG10.5% ± 0.5%9.7%–
Intec 40GSNatural gas9.5%8.7%200 ppm
Intec 40GSLPG10.5%9.4%–

CO₂ and CO from manual 1.038435 ST.001940/000, page 4, 5. Check against the data badge.

The burner pressure settings have been factory set and should not require adjusting. (page 27)

Alpha InTec² 20SE and 30SE

Covers: Intec² 20SE, Intec² 30SE

GC 41-532-28, 41-532-29

Enter Chimney Sweep Mode (Combustion Check)

  1. Without any CH or DHW demand, press and hold the reset button for eight seconds and the boiler will fire at a fixed output.
  2. The parasol and snowman symbols will flash at the same time to indicate this mode.
  3. The boiler output can then be manually controlled by turning the Central Heating control knob from the minimum CH output to the maximum CH output (display shows percentage from 00 minimum to 99 maximum).
  4. This mode will remain active for fifteen minutes or can be cancelled by turning the boiler off.

From manual 1.035664, page 28.

Enter CO2 Calibration Setup Menu

  1. Turn the DHW selector to 6 o'clock and the CH selector to 9 o'clock.
  2. Press the 'RESET' button for eight seconds until the parasol and snowman flash at the same time (chimney sweep mode).
  3. Press the 'Summer/Winter' button within three seconds to enter the setup menu.

From manual 1.035664, page 30.

Enter Fast Calibration Mode

  1. Turn the DHW selector to 6 o'clock and the CH selector to 9 o'clock.
  2. Press the 'RESET' button for eight seconds until the parasol and snowman flash at the same time (chimney sweep mode).
  3. Press the 'INFO' button within three seconds.

From manual 1.035664, page 31.

GasCO₂ max rateCO₂ min rateCO max
Natural gas9.2% ± 0.8%9.0% ± 0.8%200 ppm
LPG10.7% ± 1%10.0% ± 1%–

CO₂ and CO from manual 1.035664, page 4. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. (page )

Alpha InTec² 25XE and 28XE

Covers: Intec2 25 28XE

Enter Service / Chimney Sweep Mode

  1. Without any CH or DHW demand, press and hold the reset button for eight seconds.
  2. The parasol and (parasol/snowman) symbols will flash.
  3. Boiler output can be manually controlled by turning the Central Heating control knob (00 min to 99 max).
  4. Mode remains active for 15 minutes or cancel by turning the boiler off.

From manual 1.038088, page 28.

GasCO₂ max rateCO₂ min rateCO max
Natural gas9.1%9.0%200 ppm
LPG10.8% ± 1%10.0% ± 1%–

CO₂ and CO from manual 1.038088, page 4. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. (page 28)

Alpha Pro Tec Plus 50, 70, 90 and 115

Covers: Pro Tec 24, Pro Tec Plus

Chimney Sweep Function (Service Mode)

  1. Press and hold button 'A' to activate.
  2. Select minimum output (0%) by pressing the DHW - button.
  3. Select maximum output (100%) by pressing the DHW + button.
  4. Output values between 0% and 100% can be selected using the CH + and - buttons to change the value in 1% increments.
  5. This function can be disabled by pressing and holding in button 'A'.

From manual 1.038054, page 27.

GasCO₂ max rateCO₂ min rateCO max
Natural gas9.5%9.1%14 ppm
LPG10.6%10.1%184 ppm

CO₂ and CO from manual 1.038054, page 5. Check against the data badge.

E-Tec 20NXS, 30NXS and 35NXS

Covers: E-Tec 20NXS, E-Tec 30NXS, E-Tec 35NXS

GC 41-532-53, 41-532-54, 41-532-55

Chimney Sweep Mode (Checking combustion)

  1. Without any CH or DHW demand, press and hold the reset button for eight seconds and the boiler will fire at a fixed output.
  2. The parasol and snowman symbols will flash at the same time to indicate this mode.
  3. Using the DHW up and down buttons you can change between three predefined output levels: 0% (low fire), 80 - 90% (Max CH output), 99% (Max DHW output).
  4. This mode will remain active for fifteen minutes or can be cancelled by turning the boiler off.

From manual 1.046747, page 31.

Programming the PCB (Service/Parameter Menu)

  1. Press and hold the RESET and INFO buttons at the same time for 5 seconds until the display shows two flashing dashes (- -).
  2. Enter the password '69' using the DHW up/down buttons (first digit) and CH up/down buttons (second digit).
  3. Press the operating mode button to confirm the password and access the menu.
  4. Scroll through the four submenus (P, t, A, S) by pressing the DHW up and down buttons, and press the mode button to access the menu.
  5. Scroll through the parameters (P0-P5, t0-t9, A0-A6, S0-S2) using the DHW up and down buttons, then press the mode button to display the parameter.
  6. Press the mode button to display the parameter and adjust its value using the CH up and down buttons.
  7. Press the mode button for more than 1 second to store the parameter value (confirmation is given by '88' for 2 seconds).

From manual 1.046747, page 35.

ModelGasCO₂ max rateCO₂ min rateCO max
E-Tec 20NXSNatural gas9.5% ± 0.49.1% ± 0.1250 ppm
E-Tec 20NXSLPG10.4% ± 0.210.0% ± 0.2250 ppm
E-Tec 30NXS, E-Tec 35NXSNatural gas9.2% ± 9.1 to 9.58.5% ± 8.3 to 8.7250 ppm
E-Tec 30NXS, E-Tec 35NXSLPG10.2% ± 10.0 to 10.49.7% ± 9.5 to 9.9250 ppm

CO₂ and CO from manual 1.046747, page 6. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. If adjustment is recommended or required the engineer must be competent to carry out this work. (page 31)

E-Tec 20S, 30S and 35S

Covers: E-Tec 20S, E-Tec 35S

GC 41-532-47, 41-532-52

Chimney Sweep Mode (Combustion Check Mode)

  1. Without any CH or DHW demand, press and hold the reset button for eight seconds and the boiler will fire at a fixed output.
  2. The parasol and snowman symbols will flash at the same time to indicate this mode.
  3. Using the DHW up and down buttons you can change between three predefined output levels: 0% (low fire), 80 - 90% (Max CH output), and 99% (Max DHW output).
  4. This mode will remain active for fifteen minutes or can be cancelled by turning the boiler off.

From manual 1.047103 rev. ST.006282/006, page 31.

ModelGasCO₂ max rateCO₂ min rateCO max
E-Tec 20SLPG11.4% (+0.1 / -0.3)10.6% (+0.3 / -0.1)–
E-Tec 35SLPG10.9% (+0.4 / -0.2)9.9% (+0.4 / -0.2)–

CO₂ and CO from manual 1.047103 rev. ST.006282/006, page 6. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. (page )

E-Tec 28NX and 33NX

Covers: E-Tec 28NX, E-Tec 33NX

GC 47-532-80, 47-532-81, 47-532-82, 47-532-83

Chimney Sweep Mode (Combustion Checking)

  1. Without any CH or DHW demand, press and hold the reset button for eight seconds and the boiler will fire at a fixed output.
  2. The parasol and snowman symbols will flash at the same time to indicate this mode.
  3. Using the DHW up and down buttons you can change between three predefined output levels: 0% (low fire), 80 - 90% (Max CH output), and 99% (Max DHW output).
  4. This mode will remain active for fifteen minutes or can be cancelled by turning the boiler off.

From manual 1.046745, page 30.

Programming the PCB (Service/Parameter Mode)

  1. Press and hold the RESET and INFO buttons at the same time for 5 seconds; the display will show two flashing dashes (- -).
  2. Enter the password '69': use the DHW up/down buttons to enter the first digit and the CH up/down buttons to enter the second digit.
  3. Press the operating mode button to confirm the password and access the menu.
  4. Scroll through the submenus (P, t, A, S) using the DHW up and down buttons, then press the mode button to access the menu.
  5. Press the mode button to display the parameter, then adjust its value using the CH up and down buttons.
  6. Press the mode button for more than 1 second to store the parameter value (confirmation given by the numbers 88 appearing for 2 seconds).
  7. Press the RESET button to exit a parameter without changing its value, or press RESET to exit the programming mode.

From manual 1.046745, page 33.

ModelGasCO₂ max rateCO₂ min rateCO max
E-Tec 28NXNatural gas9.2% (-9.5)8.5% (-8.7)250 ppm
E-Tec 28NXLPG10.2% (-10.4)9.7% (-9.9)250 ppm
E-Tec 33NXNatural gas9.2% ± 0.28.5% ± 0.2250 ppm
E-Tec 33NXLPG10.3% ± 0.29.6% ± 0.2250 ppm

CO₂ and CO from manual 1.046745, page 5. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. If adjustment is recommended or required the engineer must be competent to carry out this work. (page 30)

Eco

Covers: Eco, Eco 11 13

GC 47-532-59

Entering Service Mode

  1. Press and hold the reset button for eight seconds.
  2. The boiler will fire at a fixed output depending on the position of the boiler central heating thermostat knob.
  3. Turn the boiler central heating thermostat to maximum to check the maximum central heating burner pressure.
  4. With the boiler central heating thermostat set to maximum, fully open a hot tap to check the maximum domestic hot water burner pressure.

From manual 1.033694, page 22.

GasCO₂ max rateCO₂ min rateCO max
Natural gas9.55%8.9%200 ppm

CO₂ and CO from manual 1.033694, page 4. Check against the data badge.

The burner pressure settings have been factory set and should not require adjusting. Replacement of a gas valve or PCB must be carried out by a Gas Safe registered engineer with the use of a flue analyser. (page 22)

InTec² 26CE, 30CE and 35CE

Covers: Intec² 26CE, Intec² 30CE, Intec² 35CE

GC 47-532-66, 47-532-67, 47-532-68

Chimney Sweep Mode (Combustion Check Mode)

  1. Without any CH or DHW demand, press and hold the reset button for eight seconds and the boiler will fire at a fixed output depending on the position of the central heating thermostat knob.
  2. The parasol and snowman symbols will flash at the same time to indicate this mode.
  3. Manually control the boiler output by turning the Central Heating control knob from the minimum CH output to the maximum CH output (display shows percentage from 00 minimum to 99 maximum).
  4. This mode remains active for fifteen minutes or can be cancelled by turning the boiler off.

From manual 1.035665, page 28.

Entering Parameter and Service Setup Menu

  1. Set the DHW selector to 6 o’clock and the CH selector to 9 o’clock.
  2. Press the 'RESET' and 'Summer/Winter' buttons simultaneously for about 8 seconds to access the parameter menu.

From manual 1.035665, page 30.

Full Calibration / CO2 Set Up Procedure

  1. Turn the DHW selector to 6 o'clock and the CH selector to 9 o'clock.
  2. Press the 'RESET' button for eight seconds until the parasol and snowman flash at the same time (chimney sweep mode).
  3. Press the 'Summer/Winter' button within three seconds to enter the setup menu.
  4. Adjust flue gas CO2 levels at maximum DHW (99%), medium, and minimum (00%) output levels using the 'Standby' and 'INFO' buttons.
  5. Press the reset button to store the setting and the 'Summer/Winter' button to save and exit.

From manual 1.035665, page 30.

Fast Calibration Mode

  1. Turn the DHW selector to 6 o'clock and the CH selector to 9 o'clock.
  2. Press the 'RESET' button for eight seconds until the parasol and snowman flash at the same time (chimney sweep mode).
  3. Press the 'INFO' button within three seconds to activate fast calibration.
  4. The boiler will automatically calibrate across max, med, and min heat output values and exit automatically.

From manual 1.035665, page 31.

ModelGasCO₂ max rateCO₂ min rateCO max
Intec² 26CE, Intec² 35CENatural gas9.2% ± 0.8%9.0% ± 0.8%200 ppm
Intec² 26CE, Intec² 35CELPG10.5% ± 1%10.0% ± 1%–
Intec² 30CENatural gas9.2% ± 0.8%9.0% ± 0.8%200 ppm
Intec² 30CELPG10.8% ± 1%10.0% ± 1%–

CO₂ and CO from manual 1.035665, page 4. Check against the data badge.

The air gas ratio of the boiler has been factory-set and should not require adjusting during commissioning. If adjustment is recommended or required the engineer must be competent to carry out this work. (page 28)

The app

Every Alpha manual, searchable on the job

Service mode, gas valve and combustion figures, fault codes and the full manual for the boiler in front of you, plus Ask Flint for anything the manual covers.

Start 7 days free

Then £3.99 a month or £29.99 a year. Cancel any time.

Common questions

Is service mode the same as chimney sweep mode?

Yes, in practice. Makers use different names for the same function: service mode, chimney sweep mode, test mode, calibration mode, check programme. Each one holds the burner at a fixed rate, usually maximum then minimum, so you can take a stable combustion reading.

Can I adjust the gas valve while it's in service mode?

Only where the manual gives an adjustment procedure, and only with an analyser in the flue. Many current boilers are set at the factory and the manual says not to touch the gas valve. Where a manual says that, it is shown with the procedure above.