Service mode › Chaffoteaux
Chaffoteaux boiler service mode
How to put a Chaffoteaux boiler into service mode, so it holds maximum or minimum rate while you take combustion readings. 21 models from 16 Chaffoteaux installation and servicing manuals, each step with the page it came from.
Grouped by manual: one manual usually covers a range of outputs. The CO₂ figures are the manual's own. Set and check them with a calibrated analyser, never by eye.
Britony 11.1 / Britony II T Multipoint Water Heater
Covers: Britony 2T
GC 52-980-18, 52-980-23
Putting into Service
- Remove protective film before use.
- Open the gas and water service taps beneath the appliance.
- Purge the gas and water supplies. Check for gas and water soundness at all heater and external pipework connections.
- Fit the gas control knob and light the pilot by turning the knob 90° anti-clockwise. It may be necessary to purge the pilot gas supply, if so, wait a few moments, return the gas control knob to the off position and repeat (the pilot supply will only purge when the gas control knob has been turned 90° anti-clockwise).
- Turn the gas control knob fully anti-clockwise to the main gas position. If the pilot is now extinguished for any reason, return the gas control knob to the safety interlock to reset itself.
- Turn on an adjacent water draw-off point, the heater will now light.
- Check the burner pressure by fitting a suitable gauge to the pressure test point on the end of the burner manifold. The correct pressure is given in Table 1 page 3. If the burner pressure is not correct, check that the pressure at the gas tap test point is 20 mbar (8 ins w.g.) with the appliance operating.
From the installation and servicing manual, page 6.
The heat input to the heater is preset and non-adjustable. (page )
Britony Combi / Chaffoteaux et Maury
Covers: 80/100, Combi 80
GC 47-980-12
Entering/Setting Service Modes (PCB Adjustments)
- Pivot down electrical box.
- Remove rear cover and rear panel of electrical box.
- Unplug connectors from regulation PCB and pull it toward you.
- Heating output limitation: Plug C on 'P MAX' (without limitation) or 'P 1/3' (1/3 gas rate).
- Burner functioning: Plug D on 'NOR' (3/3, 1/3, 0) or 'TUR' (full gas rate only).
From manual ESP036, page 41.
The boiler is fitted with a pre-adjusted by pass. Although adjustment is not normally necessary, the by pass can be reset by turning screw (D Fig 9) anticlockwise to open the by-pass (page 17)
Britony Combi SE 80 / SE 100
Covers: Britony Combi SE 80
GC 47-980-16, 47-980-18
Entering adjustment / service access
- Isolate mains electrical supply to boiler.
- Remove boiler outer casing.
- Remove rubber cover 'D' on face of electrical box.
From manual 1304415h, page 10.
Gas Rate Reduction Adjustment
- The spade connector JP3 allows the gas rate to be reduced to 1/3 performance by positioning spade across pins, or full performance across pins as shown.
From manual 1304415h, page 10.
BRITONY II FF
Covers: Britony II 50FF
GC 52-980-21
Entering/Operating Service Mode
- Turn on an adjacent hot water draw off to force the fan to high speed.
- Check burner setting pressure at the pressure test point U.
From manual 52.980.21, page 13.
The heat input to the appliance is preset and non-adjustable. (page 13)
CALYDRA GREEN
Covers: Calydra 24 Green
GC 47-980-25, 47-980-26
Accessing Combustion Rate Control Mode
- Press menu key on C.H. side once to access menu 5.
- Wait 5 seconds.
- Switching on the combustion rate control mode: Central heating output reaches the maximum power.
- Press once to switch to minimum power.
- Press once to switch to maximum power.
From manual 1311238a - 09/2003, page 15.
Centora Green
Covers: Centora Green 24, Centora Green 30
GC 47-980-21, 47-980-24
Enter and Use Combustion Rate Control Mode
- Switch to Menu 5 by pressing once and waiting 5 seconds until combustion rate control mode OFF is displayed.
- Press once to switch on the combustion rate control mode. Central heating temperature is displayed in celsius degrees, and 3 dots indicate combustion rate control is ON at maximum output.
- Press once to switch the combustion rate down to minimum power (indicated by a dot).
- Press once to switch combustion rate back to maximum output.
- Press once to switch off the combustion rate control mode.
From manual 1309033d, page 15.
Enter Installer / Setting Mode
- To gain access to setting keys, open front door P.
- Press simultaneously on '-' and '+' keys on the D.H.W. side for 5 seconds. Menu 1 is displayed.
- Press on Menu key (key on C.H. side) to change for the next menu.
From manual 1309033d, page 12.
Centora green 18-24
Covers: Talia Green 25
Enter Service Mode (Installer Mode)
- Open the front door P
- Press both the - and + keys on the D.H.W. side for 5 seconds
- Menu 1 will be displayed for the default register
From manual 1309033a, page 12.
Combustion Rate Control (Force Rate)
- Enter Installer Mode
- Press the + key (C.H. side) 4 times to enter Menu 5
- Press '-' (C.H. side) once to activate: display shows 'XX' and 3 dots for Maximum Output
- Press '-' (C.H. side) again: display shows 'XX' and 1 dot for Minimum Output
- Press '-' (C.H. side) again: returns to Maximum Output (3 dots)
- To exit, press '-' (C.H. side) again or leave keys for 15 minutes
From manual 1309033a, page 15.
Centora Green System
Covers: Centora Green System 30
GC 41-980-31
Entering Installer Setting Mode
- Open the front door P to gain access to the setting keys.
- Press simultaneously on + and - keys on the right side for 5 seconds. Menu 1 is displayed.
- Press on the menu key (left side) to change for the next menu.
From manual 1310360g- 3/2004, page 12.
Combustion Rate Control Mode (Menu 5)
- Press and wait for 5 seconds to switch on the combustion rate control mode OFF display.
- Press once to switch on the combustion rate control mode (Central heating output reaches the maximum power set in menu 4 section 9).
- Press once to switch the combustion rate down to minimum power.
- Press once to switch on the combustion rate to maximum output set in menu 4 section 9.
- Press once to switch off the combustion rate control mode.
From manual 1310360g- 3/2004, page 15.
Centora Green System 24 / 30
Covers: Centora Green System 24
GC 41-980-12
Entering Installer / Setting Mode
- Open the front door P to gain access to setting keys.
- To gain access to setting menus press simultaneously on the '-' and '+' keys on the Right side during 5 seconds. Menu 1 is displayed.
- Press on the Menu key (the '+' key on the Left side) to change for the next menu.
- Press on the '+' or '-' key on the Right side to change from a section to the previous or the next in a menu.
From manual 1310360g, page 12.
Combustion Rate Control Mode (Menu 5)
- Press once to access Menu 5, wait 5 seconds for combustion rate control mode OFF display.
- Press once to switch on combustion rate control mode (Central heating output reaches maximum power set in menu 4 section 9).
- Press once to switch combustion rate control mode down to minimum power.
- Press once to switch on combustion rate control mode to maximum output.
- Press once to switch off the combustion rate control mode.
From manual 1310360g, page 15.
Challenger Fanned Flue Boilers 30 FF / 50 FF
Covers: Challenger 30ff, Challenger 50ff
GC 41-980-74, 41-980-77
Gas rate adjustment
- Turn boiler to off by pressing OFF button.
- Remove the pressure test point screw (1) and connect a suitable pressure gauge (fig. 17).
- Remove the hexagonal cap from gas rate adjuster, (2) exposing the adjustment screw (fig. 17).
- Turn boiler on by pressing ON button.
- Adjust setting pressure. Setting pressures are given in graph relative to required output. The pressure will be reduced by clockwise movement of screw, increased by anti-clockwise movement.
- Turn boiler to OFF and refit pressure test point screw and gas rate adjuster cap and ensuring that a gas tight seal is made.
- Mark the data badge to indicate output.
- Replace front case. Particular care must be given to ensuring that the case seal is sound when the casing is replaced.
- After boiler has been running for 10 mins check the gas rate.
- Fit the plastic turret cover threading the harness through the slot provided.
- Secure cover with the thread forming screws provided.
From the installation and servicing manual, page 12.
CHALLENGER Open Flue Boilers 30 OF / 50 OF
Covers: Challenger 30of
GC 41-980-72
Gas Rate Adjustment
- Switch boiler to off by pressing OFF button.
- Remove the pressure test point screw (1) and connect a suitable pressure gauge.
- Remove the hexagonal cap from gas volume adjuster, (2) exposing the adjustment screw.
- Turn boiler on by pressing ON button.
- Adjust pressure after boiler has been running for 10 minutes. Setting pressures are given in graph relative to required output and then check the gas rate. The pressure will be reduced by clockwise movement of screw, increased by anti-clockwise movement.
- Turn boiler to OFF and refit pressure test point screw and volume regulator cap. Test for gas leakage around pressure test point.
- Mark the badge to indicate output to which boiler has been set.
From the installation and servicing manual, page 11.
CORVEC SH 12
Covers: Corvec 28 OF BF
Putting into Service
- Open the gas and water service taps. Purge the gas and water supplies. Check for gas and water soundness.
- Fit the gas control knob and light the pilot by turning 90° anti-clockwise. It may be necessary to wait for the pilot to purge, if so, wait a few moments then turn to the 'off' position and repeat.
- Turn the gas control fully anti-clockwise to the main gas position.
- Turn on the shower, the heater will now light.
- Check the burner pressure by fitting a gauge on to the pressure test point on the end of the burner manifold. The correct pressure is 12.7 mbar.
From the installation and servicing manual, page 5.
The heat input is preset and non-adjustable. (page 5)
Flexiflame 140 (System)
Covers: Flexiflame 140
GC 41-980-64
Service Mode / Commissioning Gas Rate Adjustment
- Switch off boiler at electrical control box.
- Set system circulation pump in operation and open all system control valves.
- Remove pressure test point screw from left hand burner manifold.
- Connect pressure gauge suitable for range 0–20 mbar.
- Remove hexagonal cap from gas volume governor.
- Turn on boiler.
- After 10 minutes, adjust burner pressure to value shown in graph (fig. 17).
- Clockwise reduces pressure, anti-clockwise increases.
- Turn off boiler, remove gauge, refit screw and cap.
From the installation and servicing manual, page 11.
The gas volume governor is factory-set. Adjust burner pressure by turning the adjusting screw exposed by removing the hexagonal cap on the front of the gas volume governor. Clockwise reduces pressure; anti-clockwise increases pressure. Adjust 10 minutes after lighting. (page 11)
Minima HE Condensing Wall Hung Combination Boiler
Covers: Minima HE 24, Minima HE 30, Minima HE 35
GC 47-980-33, 47-980-34, 47-980-35
Enter Combustion Rate Control Mode (Test Mode)
- Access the settings menu by pressing the + and - buttons together for 5 seconds.
- Press the menu button to access Menu 5 and press the setting button once to switch the combustion rate control mode to maximum.
From manual 1315867a, page 29.
Force Max & Min Rate
- Access the settings menu by pressing the + and - buttons together for 5 seconds
- Press the menu button to access Menu 5
- Press the setting button once to switch the combustion rate control mode to maximum
- Press the setting button once to set the combustion rate control mode to minimum
- Press the setting button again to set the combustion rate control mode back to maximum
From manual 1315867a, page 29.
| Model | Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|---|
| Minima HE 24 | Natural gas | 9.5% ± 0.2% | – | – |
| Minima HE 24 | LPG | 9.8% | – | – |
| Minima HE 30 | Natural gas | 9.2% ± 0.2% | 9.2% ± 0.2% | – |
| Minima HE 35 | Natural gas | 9.1% ± 0.2 | – | – |
| Minima HE 35 | LPG | 9.8% ± 0.2 | – | – |
CO₂ and CO from manual 1315867a, page 29, 56, 58. Check against the data badge.
The gas valve settings will need to be adjusted (see Section 14.5 page 30); Test for tightness on reassembly. (page 44)
Minima HE System Condensing Wall Hung System Boiler Installation
Covers: Minima HE System 30
GC 41-980-34
Enter Combustion Rate Control Mode (Menu 5)
- Access the setting menu by pressing the + and - buttons for 5 seconds; the flame icon will be shown in the display.
- Press the menu button four times to access Menu 5.
- Press the setting button once to switch the output of the boiler to maximum.
- Press the - button once to set the combustion control rate mode to minimum.
- Press the + button again to set the combustion rate control mode to maximum.
From manual 1316457b, page 34.
Exiting Service / Combustion Rate Control Mode
- To cancel the combustion rate control mode press the reset key.
- To exit the setting mode, do not press any buttons for 1 minute, the boiler will automatically exit the Setting Menu.
From manual 1316457b, page 43.
Minima HE System Installation
Covers: Minima HE System 24
GC 41-980-33
Accessing Combustion Rate Control Mode (Service Mode)
- Ensure the boiler is powered, gas cock open, and room thermostat calling for heat.
- Access the setting menu by pressing the + and - buttons for 5 seconds until the icon is shown in the display.
- Press the menu button four times to access Menu 5.
- Press the setting button once to switch the output of the boiler to maximum (two digits flash showing temperature, with a top cursor indicating maximum output).
- Press the setting button (-) once to set the combustion control rate mode to minimum.
- Press the setting button (+) again to set the combustion rate control mode to maximum.
- To exit the setting mode, do not press any buttons for 1 minute; the boiler will automatically exit the Setting Menu.
From manual 1316457b - 03/2005, page 34.
Nothing matches that. The app covers more Chaffoteaux models than have a service-mode procedure here.
The app
Every Chaffoteaux manual, searchable on the job
Service mode, gas valve and combustion figures, fault codes and the full manual for the boiler in front of you, plus Ask Flint for anything the manual covers.
Start 7 days freeThen £3.99 a month or £29.99 a year. Cancel any time.
Common questions
Is service mode the same as chimney sweep mode?
Yes, in practice. Makers use different names for the same function: service mode, chimney sweep mode, test mode, calibration mode, check programme. Each one holds the burner at a fixed rate, usually maximum then minimum, so you can take a stable combustion reading.
Can I adjust the gas valve while it's in service mode?
Only where the manual gives an adjustment procedure, and only with an analyser in the flue. Many current boilers are set at the factory and the manual says not to touch the gas valve. Where a manual says that, it is shown with the procedure above.