Baxi boiler service mode
How to put a Baxi boiler into service mode, so it holds maximum or minimum rate while you take combustion readings. 153 models from 52 Baxi installation and servicing manuals, each step with the page it came from.
Grouped by manual: one manual usually covers a range of outputs. The CO₂ figures are the manual's own. Set and check them with a calibrated analyser, never by eye.
& Boiler Fiche - Combi 2/2.1
Covers: 424 COMBI 2.1, 430 COMBI 2.1, 436 COMBI 2.1, ASSURE 524 COMBI 2, ASSURE 530 COMBI 2, ASSURE 536 COMBI 2
GC 47-077-59, 47-077-60, 47-077-61, 47-077-74, 47-077-75, 47-077-76
Activating the chimney sweep mode
- Press the two F1 + F2 keys simultaneously until the function activates.
- When the letter L appears on the display followed by the flow temperature, the boiler is working at minimum power.
- Turn the heating knob one notch to the right. When the letter h appears on the display followed by the flow temperature, the boiler is working at maximum power in HEATING MODE.
- Turn the heating knob another notch to the right. When the letter H appears on the display followed by the flow temperature, the boiler is working at maximum power in DOMESTIC HOT WATER MODE.
- To activate the domestic water mode, configure the setting to GP082=1. Once finished, return the setting to GP082=0.
- To finish and exit the function press the F1 key.
From manual 7875578-02, page 35.
Forcing Maximum and Minimum Rate (Chimney Sweep Mode)
- Minimum power: Press F1 + F2 until 'L' is displayed.
- Maximum CH power: Turn heating knob one notch to the right until 'h' is displayed.
- Maximum DHW power: Turn heating knob another notch to the right until 'H' is displayed.
From manual 7875578-02, page 35.
| Model | Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|---|
| 424 COMBI 2.1 | Natural gas | 8.8% | 8.1% | 350 ppm |
| 424 COMBI 2.1 | LPG | 10.3% ± (10.2 to 10.7) | 9.7% ± (9.2 to 9.8) | – |
| 430 COMBI 2.1 | Natural gas | 9.4% | 8.8% | 350 ppm |
| 436 COMBI 2.1 | Natural gas | 9.4% | 8.8% | 350 ppm |
| 436 COMBI 2.1 | LPG | 10.3% ± 10.2 to 10.7 | 9.7% ± 9.2 to 9.8 | 350 ppm |
| ASSURE 524 COMBI 2 | Natural gas | 8.8% | 8.1% | 350 ppm |
| ASSURE 524 COMBI 2 | LPG | 10.0% ± (10.0 to 10.5) | 9.6% ± (9.2 to 9.8) | – |
| ASSURE 530 COMBI 2 | Natural gas | 8.8% | 8.1% | 350 ppm |
| ASSURE 530 COMBI 2 | LPG | 10.0% ± 10.0 to 10.5 | 9.2% ± 9.2 to 9.8 | – |
| ASSURE 536 COMBI 2 | Natural gas | 8.8% | 8.1% | 350 ppm |
CO₂ and CO from manual 7875578-02, page 36, 38. Check against the data badge.
Always adjust the maximum CO2 before making any alteration to the minimum value. (page 38)
800 System 2
Covers: 818 System 2, 824 System 2, 830 System 2
GC 41-470-99, 41-884-08, 41-884-09
Activating the chimney sweep function (forced full load or low load)
- Press the two F1 + F2 keys simultaneously until the function activates.
- When the letter L appears on the display (followed by the flow temperature) the boiler is working at minimum power.
- Turn the heating knob one notch to the right. When the letter h appears on the display (followed by the flow temperature) the boiler is working at maximum power in HEATING MODE.
- Turn the heating knob another notch to the right. When the letter H appears on the display (followed by the flow temperature) the boiler is working at maximum power in DOMESTIC WATER MODE (configure setting GP082=1 to activate domestic water mode, and return to GP082=0 when finished).
- To finish and exit the function press the F1 key.
From the installation and servicing manual, page 46.
Assure 518 System 2 & Boiler Fiche
Covers: 624 System 2, Assure 515 System 2, Assure 518 System 2, Assure 524 System 2
GC 41-844-04, 41-844-05, 41-844-06, 41-884-03
Activating the chimney sweep mode
- Press the two F1 + F2 keys simultaneously until the function activates.
- When the letter L appears on the display (followed by the flow temperature) the boiler is working at minimum power.
- Turn the heating knob one notch to the right. When the letter h appears on the display (followed by the flow temperature) the boiler is working at maximum power in HEATING MODE.
- Turn the heating knob another notch to the right. When the letter H appears on the display (followed by the flow temperature) the boiler is working at maximum power in DOMESTIC HOT WATER MODE.
- To finish and exit the function press the F1 key.
From manual 7875579-01, page 34.
Accessing installer settings / parameter configuration
- Press the F3 key — the symbol on the menu bar will start to flash.
- Turn the knob until the installer settings symbol is reached then press F4 key to confirm.
- Use the knob to enter code 0012 and confirm by pressing the F4 key.
- Turn the knob until the desired setting is reached then press F4 key to confirm.
From manual 7875579-01, page 42.
| Model | Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|---|
| 624 System 2, Assure 515 System 2, Assure 518 System 2 | Natural gas | 8.8% | 8.1% | 350 ppm |
| Assure 524 System 2 | Natural gas | 8.8% | 8.1% | 350 ppm |
| Assure 524 System 2 | LPG | 10.3% ± 10.2 to 10.7 | 9.7% ± 9.2 to 9.8 | 350 ppm |
CO₂ and CO from manual 7875579-01, page 35, 37. Check against the data badge.
When the gas-air ratio is completely out of setting, it is possible to use the adjustment procedure: With the boiler off, turn the adjustment screw (V) clockwise till the stop. The screw head is flush with the surrounding plastic tube. To restore the appliance to factory conditions, turn the adjustment screw (V) anticlockwise for System 18: Natural Gas (G20): 6 turns, LPG (G31): 8 turns. (page 57)
Assure Heat
Covers: Assure 13 Heat, Assure 16 Heat, Assure 19 Heat, Assure 25 Heat, Assure 30 Heat
GC 41-470-80, 41-470-81, 41-470-82, 41-470-83, 41-470-84
Enter Chimney Sweep Mode (CSM)
- Press the Chimney Sweep button for 3 seconds.
- CSM is activated and will go to the min rate.
- Pressing again will make it adjust to max rate.
- To exit press the RESET for 3 seconds.
From manual 7749545-01, page 43.
Force Max & Min Rate (Chimney Sweep Mode)
- Press the Chimney Sweep button for approximately 3 seconds to select minimum rate (status signal is orange and flashes green briefly).
- Press the Chimney Sweep button again once to select maximum rate (status light goes off briefly once).
From manual 7749545-01, page 55.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.3% ± 0.1% | 8.9% ± 0.1% | 350 ppm |
CO₂ and CO from manual 7749545-01, page 55. Check against the data badge.
The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. (page 42)
Baxi 124 - 128 Combi Condensing Combination Boiler
Covers: 124 Combi, 128 Combi
GC 47-077-25, 47-077-26
Enter Chimney Sweep Function (Force Max Rate)
- Press the 'i P' button and the 'IIII°+' button together and hold for at least 6 seconds.
- 'On' will be displayed briefly, followed by '304' then '100' when the boiler is lit, indicating the CH output is at MAXIMUM ('Chimney Sweep Function').
From manual 7659607-02, page 30.
Select Ignition Phase and Minimum Rate in Chimney Sweep Function
- While in the function, press to select the Ignition Phase Speed.
- Press again to select the Minimum Output ('00').
From manual 7659607-02, page 43.
Exit Service / Chimney Sweep Function
- Press the i P button and the IIII°+ button together and hold for at least 6 seconds to exit the function.
From manual 7659607-02, page 30.
| Model | Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|---|
| 124 Combi | Natural gas | 9.0% ± 0.7 | – | 350 ppm |
| 124 Combi | LPG | 10.5% ± 1.0 | – | 350 ppm |
| 128 Combi | Natural gas | 9.0% ± 0.7 | 9.0% ± 0.7 | 350 ppm |
| 128 Combi | LPG | 10.5% ± 1.0 | 10.5% ± 1.0 | 350 ppm |
CO₂ and CO from manual 7659607-02, page 10, 43. Check against the data badge.
IMPORTANT: The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. Do not adjust the air/gas ratio valve. (page 28)
Baxi 200 Heat Condensing Central Heating Boiler 212 - 215 - 218 - 224 - 230
Covers: Heat 212, Heat 215, Heat 218, Heat 224, Heat 230
GC 41-470-45, 41-470-46, 41-470-47, 41-470-48, 41-470-49
Entering Chimney Sweep Mode (Force Max & Min Rate)
- Press the Chimney Sweep button for approximately 3 seconds. CSM is activated and will go to the min rate (status signal is orange and flashes green briefly).
- Pressing the Chimney Sweep button again once will make it adjust to max rate (orange status light goes off briefly once and maximum rate is selected).
- Press the Chimney Sweep button twice to select the minimum rate from max rate.
- To exit press the RESET button for 3 seconds or briefly press the RESET button to return the boiler to normal operating status.
From manual 7684224-01, page 42.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.3% ± 0.1% | 8.9% ± 0.1% | 350 ppm |
CO₂ and CO from manual 7684224-01, page 54. Check against the data badge.
If the boiler will not light, prior to final setting, use a suitable hexagon key to wind out the Throttle Adjustment Screw until it is flush with the valve body, then turn the screw 4 full turns clockwise. (page 53)
Baxi 400 Heat Gas Fired Wall Mounted Condensing Boiler
Covers: Heat 412, Heat 415, Heat 418, Heat 424, Heat 430
GC 41-470-50, 41-470-51, 41-470-52, 41-470-53, 41-470-54
Chimney Sweep Mode (CSM) - Enter/Exit and Force Max/Min Rate
- Press the Chimney Sweep button for 3 seconds to activate CSM; it will go to the minimum rate (status signal is orange and flashes green briefly).
- Press the Chimney Sweep button again once to adjust to the maximum rate (orange status light goes off briefly once and maximum rate is selected).
- Briefly press the RESET button or press the RESET for 3 seconds to exit.
From manual 7684223-01, page 43.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.3% ± 0.1 | 8.9% ± 0.1 | 350 ppm |
CO₂ and CO from manual 7684223-01, page 55. Check against the data badge.
The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. (page 42)
Baxi 50 HE Plus, 80 HE Plus, 100/2 HE Plus
Covers: 50 HE Plus
GC 41-077-41
Operating Control Knob (Service / Commissioning)
- Turn the boiler control knob fully clockwise to 'HIGH' to run the system and check correct operation.
From the installation and servicing manual, page 31.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.0% ± 1% | 9.0% ± 1% | – |
CO₂ and CO from the installation and servicing manual, page 6. Check against the data badge.
No adjustment of the gas valve is permissible. (page 31)
Baxi 600 Combi 2
Covers: 624 Combi 2, 630 Combi 2, 636 Combi 2
GC 47-077-55, 47-077-56, 47-077-57
Activating the chimney sweep function
- Press the two F1 + F2 keys simultaneously until the function activates.
- When the letter L appears on the display (followed by the flow temperature) the boiler is working at minimum power.
- Turn the HEATING knob one notch to the right. When the letter h appears on the display (followed by the flow temperature) the boiler is working at maximum power in HEATING MODE.
- Turn the HEATING knob another notch to the right. When the letter H appears on the display (followed by the flow temperature) the boiler is working at maximum power in DOMESTIC WATER MODE.
- To finish and exit the function press the F1 key.
From manual 7796561, page 47.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.8% | 8.0% | 350 ppm |
CO₂ and CO from manual 7796561, page 51. Check against the data badge.
Under these circumstances it is recommended NOT to adjust the gas control valve. (page 12)
Baxi 600 Heat 613 - 616 - 619 - 625 - 630
Covers: 613 Heat, 616 Heat, 619 Heat, 625 Heat, 630 Heat
GC 41-470-66, 41-470-67, 41-470-68, 41-470-69, 41-470-70
Entering Chimney Sweep Mode (Max / Min Rate)
- Press the chimney sweep button for 3 seconds.
- CSM is activated and will go to the min rate.
- Pressing the chimney sweep button again will make it adjust to max rate.
- To exit, press the RESET button for 3 seconds.
From manual 7726858, page 44.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.3% ± 0.1 | 8.9% ± 0.1 | 350 ppm |
CO₂ and CO from manual 7726858, page 56. Check against the data badge.
Baxi 600 System 2 High-efficiency wall-hung condensing gas boiler
Covers: 615 System 2, 618 System 2
GC 41-884-01, 41-884-02
Activating the chimney sweep function
- Press the two F1 + F2 keys simultaneously until the function activates.
- When the letter L appears on the display (followed by the flow temperature) the boiler is working at minimum power.
- Turn the heating knob one notch to the right. When the letter h appears on the display (followed by the flow temperature) the boiler is working at maximum power in HEATING MODE.
- Turn the heating knob another notch to the right. When the letter H appears on the display (followed by the flow temperature) the boiler is working at maximum power in DOMESTIC WATER MODE.
- To finish and exit the function press the F1 key.
From manual 7801992, page 46.
Accessing the service / installer settings
- Press the F3 key, the menu symbol starts to flash.
- Turn the domestic hot water knob until you reach the installer symbol, then press the F4 key to confirm.
- Use the domestic hot water knob to enter code 0012 and confirm by pressing the F4 key.
- Turn the domestic hot water knob until you reach the desired setting, then press the F4 key to confirm.
- Modify the value of the setting using the domestic hot water knob.
- Press F4 to confirm.
- Press F1 to exit.
From manual 7801992, page 55.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.4% | 8.8% | 350 ppm |
CO₂ and CO from manual 7801992, page 50. Check against the data badge.
Under circumstances where 20% of H2 is in the gas, it is recommended NOT to adjust the gas control valve. (page 12)
Baxi 800 Combi 2 & Boiler Fiche
Covers: 824 Combi 2, 830 Combi 2, 836 Combi 2
GC 47-077-63, 47-077-64, 47-077-65
Activating the chimney sweep function
- Press the two F1 + F2 keys simultaneously until the function activates.
- When the letter L appears on the display (followed by the flow temperature) the boiler is working at minimum power.
- Turn the heating knob one notch to the right. When the letter h appears on the display (followed by the flow temperature) the boiler is working at maximum power in HEATING MODE.
- Turn the heating knob another notch to the right. When the letter H appears on the display (followed by the flow temperature) the boiler is working at maximum power in DOMESTIC WATER MODE.
- To activate the domestic water mode, configure the setting to GP082=1. Once finished, return the setting to GP082=0.
- To finish and exit the function press the F1 key.
From manual 7821592, page 47.
Accessing the settings and installer menu
- Press the F3 key, the menu symbol starts to flash.
- Turn the knob until you reach the installer symbol, then press the F4 key to confirm.
- Use the knob to enter code 0012 and confirm by pressing the F4 key.
- Turn the knob until you reach the desired setting, then press the F4 key to confirm.
- Modify the value of the setting using the knob.
- Press F4 to confirm.
- Press F1 to exit.
From manual 7821592, page 56.
The gas valve may need to be adjusted more accurately. This must be adjusted using standard O2 values for the gas used. (page 50)
Baxi 800 Heat (816 - 825 - 830)
Covers: 816 Heat, 825 Heat, 830 Heat
GC 41-470-77, 41-470-78, 41-470-79
Chimney Sweep Mode (CSM)
- Press the chimney sweep button for 3 seconds.
- CSM is activated and will go to the min rate.
- Pressing again will make it adjust to max rate.
- To exit press the RESET for 3 seconds.
From manual 7749898-01, page 43.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.3% ± 0.1% | 8.9% ± 0.1% | 350 ppm |
CO₂ and CO from manual 7749898-01, page 55. Check against the data badge.
The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. (page 42)
Baxi Assure Combi 25 - 30 - 36 / 25 LPG - 30 LPG - 36 LPG
Covers: Assure 25 Combi, Assure 30 Combi, Assure 36 Combi
GC 47-077-42, 47-077-43, 47-077-44, 47-077-45, 47-077-46, 47-077-47
Entering Chimney Sweep Mode (Maximum and Minimum Output)
- Turn both control knobs fully anticlockwise and leave for 10 seconds.
- Turn the DHW knob (tap symbol) 1/4 turn twice in quick succession (within 2 seconds).
- "304" will appear in the display.
- Turn the CH knob (radiator symbol) fully clockwise. "100" will appear in the display, indicating maximum output.
- After checking at maximum turn the CH knob (radiator symbol) fully anticlockwise. "0" will appear in the display, indicating minimum output.
From manual 7750729-01, page 50.
Entering Calibration Mode (Gas Valve CO2 Adjustment)
- Ensure that all external controls are calling for heat. The actual current boiler temperature is shown on the display.
- Turn both control knobs fully anticlockwise, then quickly turn the right hand knob 1/4 clockwise twice and back in quick succession (within 2 seconds). "304" will appear in the display screen.
- Turn the left hand knob fully clockwise. "100" will appear in the display screen, indicating maximum output.
- To check minimum rate, turn the left hand knob fully anticlockwise. As the knob is turned the display will change, indicating the fan speed. When the display reads "0" the boiler runs at minimum rate.
- The calibration function is maintained for 20 minutes unless the maximum central heating temperature is exceeded. The function can be disabled at any time by turning the right hand knob.
From manual 7750729-01, page 62.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.0% (+0.3) | 8.5% (+0.1) | 350 ppm |
| LPG | 10.5% (+0.5) | 10.0% (+0.1) | 350 ppm |
CO₂ and CO from manual 7750729-01, page 62, 78. Check against the data badge.
After replacing the gas valve the CO2 must be checked and adjusted. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person. (page 61)
Baxi Assure System 12 - 15 - 18 - 24 / 18 - 24 LPG
Covers: Assure 12 System, Assure 15 System, Assure 24 System
GC 41-470-85, 41-470-86, 41-470-88, 41-470-93
Checking combustion - chimney sweep mode (Maximum and Minimum output)
- Turn both control knobs fully anticlockwise and leave for 10 seconds.
- Turn the right hand knob 1/4 turn twice in quick succession (within 2 seconds).
- "304" will appear in the display.
- Turn the CH knob fully clockwise. "100" will appear in the display, indicating maximum output.
- After checking at maximum turn the CH knob fully anticlockwise. "0" will appear in the display, indicating minimum output.
- Once all relevant tests are completed, take out of chimney sweep mode by turning the DHW control knob clockwise.
From manual 7750878-01, page 44.
Calibration mode / Gas valve setting
- Ensure that all external controls are calling for heat.
- Turn both control knobs fully anticlockwise, then quickly turn the right hand knob 1/4 clockwise twice and back in quick succession (within 2 seconds). "304" will appear in the display screen.
- Turn the left hand knob fully clockwise. "100" will appear in the display screen, indicating maximum output.
- Adjust maximum CO2 using the Throttle Adjustment Screw.
- Turn the left hand knob fully anticlockwise to run the boiler at minimum rate ("0" on display).
- Adjust minimum CO2 using the Offset Adjustment Screw.
From manual 7750878-01, page 54.
| Model | Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|---|
| Assure 12 System, Assure 24 System | Natural gas | 9.0% (+0.3) | 8.5% (+0.1) | 350 ppm |
| Assure 12 System, Assure 24 System | LPG | 10.5% (+0.5) | 10.0% (+0.1) | 350 ppm |
| Assure 15 System | Natural gas | 9.0% (+0.3) | 8.5% (+0.1) | 350 ppm |
CO₂ and CO from manual 7750878-01, page 53, 67. Check against the data badge.
After replacing the gas valve the CO2 must be checked and adjusted. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person. (page 53)
Baxi Bermuda 45/3 & 57/3 Boilers Gas Fired Central Heating Unit
Covers: Bermuda 45/3E, Bermuda 57/3E
GC 44-077-60, 44-077-62
Entering Service Mode / Operating Burner for Commissioning
- Turn the gas service cock 1/4 turn from the OFF position to supply gas to the boiler only.
- Purge the air from the gas service pipe in accordance with BS 6891 and test for gas soundness.
- Turn the boiler thermostat to the OFF position.
- Ensure that all external controls e.g. room stat, timer etc are calling for heat and turn on the mains electrical supply.
- Slacken the test point sealing screw and connect a pressure gauge.
- For manual control models: Hold in the grey button on the gas control valve, press the igniter button until the pilot lights, and hold the grey button for a further 15 seconds.
- For electronic control models: Turn the thermostat to HIGH to light the intermittent pilot and main burner.
- Operate the burner by turning the boiler thermostat knob to the HIGH setting and check the burner setting pressure, adjusting if necessary via the governor cover screw.
From the installation and servicing manual, page 23.
Each appliance is preset at its MIDRANGE heat input rate and is designed for use on NATURAL GAS only. (page 4)
Baxi Bermuda 45/4 & 57/4 Boilers Gas Fired Central Heating Unit
Covers: Bermuda 57/4M
GC 44-077-72
Entering Service / Operating Burner (Manual Control Models)
- Turn the gas service cock 1/4 turn from the OFF position to supply gas to the boiler only.
- Purge the air from the gas service pipe in accordance with BS 6891 and test for gas soundness.
- Turn the boiler thermostat to the OFF position.
- Ensure that all external controls (room thermostat, timer, etc.) are calling for heat and turn on the mains electrical supply.
- Slacken the test point sealing screw and connect a pressure gauge.
- Hold in the grey button on the gas control valve.
- Press the piezo igniter button and release; repeat until the pilot lights, then hold in the grey button for a further 15 seconds.
- The pilot should remain alight; if not, turn the grey button clockwise and wait 3 minutes before repeating the sequence.
- Operate the burner by turning the boiler thermostat knob to the HIGH setting and check the operation of the flame failure device by turning the grey button clockwise; the burner and pilot should extinguish.
- Turn the boiler thermostat to the 'O' position, wait 3 minutes, and relight the pilot as previously described; turn the boiler thermostat to HIGH and check the burner setting pressure, adjusting if necessary by removing the governor cover screw and adjusting the governor (clockwise to increase, anticlockwise to decrease).
- Remove the pressure gauge and tighten the pressure test point sealing screw.
From manual Comp No 241794, page 23.
Forcing Rate / Setting Pressure
- Slacken the test point sealing screw and connect a pressure gauge.
- Operate the burner by turning the boiler thermostat knob to the HIGH setting and check the operation of the flame failure device by turning the grey button (Grey Push) clockwise. The burner and pilot should extinguish.
- Turn the boiler thermostat to the "O" position, wait 3 minutes and relight the pilot as previously described.
- Turn the boiler thermostat to HIGH and check the burner setting pressure, adjusting if necessary by removing the governor cover screw and adjusting the governor (clockwise to increase, anticlockwise to decrease).
- Remove the pressure gauge and tighten the pressure test point sealing screw.
From manual Comp No 241794, page 23.
Entering Service / Operating Burner (Electronic Controls Models)
- Ensure external controls are calling for heat and turn on mains electrical supply.
- Turn the thermostat to HIGH to operate the pilot and main burner.
From manual Comp No 241794, page 24.
Baxi Bermuda BBU 15 HE
Covers: Bermuda BBU 15 HE
GC 44-075-09
Enter Calibration Mode
- Ensure external controls are calling for heat.
- Turn both control knobs fully anticlockwise.
- Turn right hand knob 1/4 clockwise twice.
- Turn right hand knob back fully anticlockwise.
- Display will alternate between 'SF' and current temperature.
- Green LEDs will flash.
From manual 7101615 - 04 (2/14), page 35.
Force Rate in Calibration Mode
- Max Rate: Turn left hand knob fully clockwise. Display shows '00'.
- Min Rate: Turn left hand knob fully anticlockwise. Display shows '0'.
From manual 7101615 - 04 (2/14), page 27.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.3% ± 0.2 | 8.2% ± 0.2 | 350 ppm |
CO₂ and CO from manual 7101615 - 04 (2/14), page 35. Check against the data badge.
IMPORTANT: The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. It is still necessary to check combustion as part of commissioning. Do not adjust the air/gas ratio valve. (page 27)
Baxi Combi 105 HE
Covers: Combi 105 HE
GC 47-075-18
Force Max/Min Burner Pressure Check
- Slacken pressure test point sealing screw on gas valve and connect gauge.
- Turn selector switch fully anticlockwise to reset.
- Turn selector to CH and DHW position.
- For Max Rate: Ensure flow rate at tap is at least 10l/min. Adjust large (8mm) nut on valve.
- For Min Rate: Remove one modulator wire. Adjust small (5mm) nut on valve.
From manual 5111809, page 25.
The factory-set gas valve must not be tampered with. Adjustments to burner pressure must be made via the adjustment nuts on the valve as per section 9.2. (page )
Baxi Combi 2
Covers: 424 Combi 2, 430 Combi 2
GC 47-077-51, 47-077-52
Activating the chimney sweep function (forced max/min rate)
- Press Back and Manual reset keys simultaneously.
- When the letter L appears on the display (followed by the flow temperature) the boiler is working at minimum power.
- Turn the heating knob one notch to the right. When the letter h appears on the display, the boiler is working at maximum power in HEATING MODE.
- Turn the heating knob another notch to the right. When the letter H appears on the display, the boiler is working at maximum power in DOMESTIC WATER MODE.
- To finish and exit the function press the Back key.
From manual 7791870, page 45.
Accessing the installer settings
- Press the menu key, the menu bar starts to flash.
- Turn the knob until you reach the installer settings symbol, then press to confirm.
- Use knob to enter code 0012 and confirm by pressing the key.
- Turn the knob until you reach the desired setting, then press to confirm.
From manual 7791870, page 53.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.0% (-9.4) | 8.5% (-8.6) | 250 ppm |
| LPG | 10.3% (-10.7) | 9.7% (-9.8) | 350 ppm |
CO₂ and CO from manual 7791870, page 47. Check against the data badge.
Under these conditions, it is recommended NOT to adjust the gas control valve (Due to variations in the percentage of H2, the percentage of O2 may vary over time. For example: 20% of H2 in the gas may lead to a 1.5% increase of O2 in the flue gases). (page 12)
Baxi Combi 624 - 630 - 636
Covers: 636 COMBI
GC 47-077-30, 47-077-31
Entering Chimney Sweep Mode (Calibration)
- Turn both control knobs fully anticlockwise and leave for 10 seconds.
- Turn the DHW knob (tap symbol) 1/4 turn twice in quick succession (within 2 seconds).
- "304" will appear in the display.
- Turn the CH knob (radiator symbol) fully clockwise. "100" will appear in the display, indicating maximum output.
- After checking at maximum turn the CH knob (radiator symbol) fully anticlockwise. "0" will appear in the display, indicating minimum output.
From manual 7717521-03, page 50.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.0% | 8.5% | 350 ppm |
| LPG | 10.5% | 10.0% | 350 ppm |
CO₂ and CO from manual 7717521-03, page 62, 76. Check against the data badge.
The gas valve is factory set for use on Natural Gas (G20) or LPG (G31). After replacing the gas valve the CO2 must be checked and adjusted. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person. (page 61)
Baxi Combi 624 — 630
Covers: 624 Combi
GC 47-077-28, 47-077-33
Entering Chimney Sweep Mode
- Turn both control knobs fully anticlockwise and leave for 10 seconds
- Turn the DHW knob (tap icon) 1/4 turn twice in quick succession (within 2 seconds)
- 304 will appear in the display
- Turn the CH knob fully clockwise to set Max output (100) or anticlockwise to set Min output (0)
From manual 7679306 - 1 - 10082017, page 50.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.0% | 8.5% | 350 ppm |
CO₂ and CO from manual 7679306 - 1 - 10082017, page 62. Check against the data badge.
The CO2 must be only checked and adjusted to set the valve if a suitable calibrated combustion analyser is available, operated by a competent person. (page 62)
Baxi Combi 80Eco Gas Fired Wall Mounted Combination Boiler
Covers: Combi 80 Eco
GC 47-075-05
Checking and Adjusting Burner Pressure (Max and Min Rate)
- Set the hot water and central heating temperature controls to maximum and the selector switch to the OFF position.
- Slacken the pressure test point sealing screw on the gas valve and connect a pressure gauge.
- Disconnect the sensing tube from the gas valve.
- Turn the selector switch fully anticlockwise against the spring pressure to the reset position and hold for 2 seconds to reset the boiler.
- Turn the selector switch to the Central Heating and Domestic Hot Water position.
- Turn on a hot water tap to give a flow rate of at least 10 l/min.
- Remove the governor cover screw and adjust the pressure regulator screw until the maximum pressure is achieved.
- Turn the boiler selector to the Off position and remove the plug from the NTC sensor.
- Turn the boiler selector switch to the Central Heating and Domestic Hot Water position and reconnect the plug to the NTC. Check and adjust as required the minimum pressure (within 25 seconds).
- Disconnect the pressure gauge, tighten the pressure test screw and replace the sensing tube on the gas valve.
- Replace the governor cover screw and set the selector switch to the position required.
From manual Comp No 247936 - Iss 6 - 6/02, page 23.
Baxi Duo-tec Combi ErP 24 - 28 - 33 - 40 / 28 LPG
Covers: Duo-tec 24 Combi ErP, Duo-tec 28 Combi ErP, Duo-tec 33 Combi ErP, Duo-tec 40 Combi ErP
GC 47-075-96, 47-075-97, 47-075-98, 47-075-99, 47-077-03
Enter Calibration / Service Mode (Maximum and Minimum Rate)
- Ensure that all external controls are calling for heat. The actual current boiler temperature is shown on the display.
- Turn both control knobs fully anticlockwise, then quickly turn the right hand knob 1/4 clockwise twice and back fully anticlockwise.
- The display will now alternate between 'SF' and the current boiler temperature and both green LEDs will flash.
- To set to maximum rate: Turn the left hand knob fully clockwise. As the knob is turned the display will change, indicating the fan speed. The display will show '00', indicating maximum rate, then revert to 'P' alternating with the current boiler temperature.
- To set to minimum rate: Turn the left hand knob fully anti-clockwise. As the knob is turned the display will change, indicating the fan speed. When the display reads ' 0' the boiler runs at minimum rate.
- This function is maintained for 20 minutes unless the maximum CH temperature is exceeded. The function can be disabled at any time by turning the right hand knob.
From manual 7647620-04, page 29.
| Model | Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|---|
| Duo-tec 24 Combi ErP, Duo-tec 28 Combi ErP, Duo-tec 33 Combi ErP | Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | 350 ppm |
| Duo-tec 24 Combi ErP, Duo-tec 28 Combi ErP, Duo-tec 33 Combi ErP | LPG | 10.0% ± 0.2 | 9.8% ± 0.2 | – |
| Duo-tec 40 Combi ErP | Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | 350 ppm |
| Duo-tec 40 Combi ErP | LPG | 10% ± 0.2 | 9.8% ± 0.2 | – |
CO₂ and CO from manual 7647620-04, page 10, 44, 53. Check against the data badge.
To assist the boiler to light prior to final setting, use a suitable hexagon key to wind out the Throttle Adjustment Screw until it is flush with the valve body, then turn the screw 4 full turns clockwise. If the boiler will not light, or the correct CO2 cannot be achieved contact Baxi Customer Support 0344 871 1545. (page 43)
Baxi Duo-tec Combi HE Range Gas Fired Wall Mounted Condensing Combination Boiler
Covers: Duo-tec Combi 24 HE, Duo-tec Combi 28 HE, Duo-tec Combi 33 HE, Duo-tec Combi 40 HE
GC 47-075-23, 47-075-24, 47-075-25, 47-075-26, 47-075-39
Enter Calibration / Service Mode (Force Max and Min Rate)
- Ensure that the integral timer and any external controls are calling for heat, and the selector switch is in the central heating and hot water position.
- Turn both temperature control knobs fully anticlockwise.
- Quickly turn the DHW temperature knob 1/4 clockwise twice and back fully anticlockwise.
- The display will now alternate between 'SF' and the current boiler temperature and both green LEDs will flash.
- Turn CH temperature control knob fully clockwise to indicate maximum rate ('00' on display, then 'P' alternating with current boiler temperature).
- Turn the CH temperature knob fully anti-clockwise to run at minimum rate (display reads '0').
- The Calibration Function is active for 20 minutes unless the maximum CH temperature is exceeded.
- The function can be disabled at any time by turning the DHW temperature knob.
From the installation and servicing manual, page 34.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | – |
CO₂ and CO from the installation and servicing manual, page 59. Check against the data badge.
The gas valve is factory set and the burner pressure cannot be measured as it is altered by suction of the fan and modulates as demand on the boiler alters. (page 34)
Baxi EcoBlue Plus Combi 24 - 28 - 33 Gas Fired Wall Mounted Condensing Combination Boiler
Covers: EcoBlue + 24 Combi ErP, EcoBlue + 28 Combi ErP, EcoBlue + 33 Combi ErP
GC 47-077-08, 47-077-09, 47-077-10
Enter Chimney Sweep Mode (Force Max/Min Rate)
- Press R & IIII- together and hold for at least 6 seconds.
- On is displayed briefly followed by 303 and the current setting point (eg. 1, 2 or 3) flashing alternately.
- To adjust the boiler input setting, press the IIII- or IIII+ button and the current setting point will flash (eg. 1, 2 or 3). Press the IIII- or IIII+ button again to alter the boiler input setting (3 = MAX. HEATING input, 2 = MAX. DHW input, 1 = MIN. input).
From manual 7219706 - 03, page 45.
Exit Chimney Sweep Mode
- Press the R button & the |||'- button together for at least 6 seconds to exit.
- Press the R button once to bring the boiler out of 'Standby' mode.
From manual 7219706 - 03, page 45.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | 350 ppm |
CO₂ and CO from manual 7219706 - 03, page 64. Check against the data badge.
After replacing the valve the CO2 must be checked and adjusted as detailed in Section 10.3.25 Setting the Gas Valve. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person. (page )
Baxi HE Range Wall Mounted Powered Flue Condensing Boilers Gas Fired Central Heating Units (Solo 30 HE)
Covers: Solo 15 HE, Solo 30 HE
GC 41-075-44, 41-075-46
Boiler Operation / Service Controls
- Turn the boiler control knob fully clockwise to 'HIGH' to run the system and check correct operation.
- Isolate both gas and electrical supplies before starting annual servicing or component replacement.
- To gain access to internal components, remove the outer case, lower door panel, and release the four 1/4 turn screws securing the air box door panel.
- Hinge down the PCB housing by removing the top right hand securing screw to access gas service cock, jumpers, and electrical connections.
From manual 5120309, page 37.
| Model | Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|---|
| Solo 15 HE | Natural gas | 9.0% ± 1% | 8.0% ± 1% | – |
| Solo 30 HE | Natural gas | 9.0% ± 1% | – | – |
CO₂ and CO from manual 5120309, page 6. Check against the data badge.
No adjustment of the gas valve is permissible. (page 37)
Baxi Megaflo 15 - 18 - 24 - 28 - 32 System ErP
Covers: Megaflo 15 System ErP, Megaflo 18 System ErP, Megaflo 24 System ErP, Megaflo 28 System ErP, Megaflo 32 System ErP
GC 41-470-18, 41-470-19, 41-470-20, 41-470-21, 41-470-22
Entering Calibration / Service Mode (Max & Min Rate)
- Ensure that all external controls are calling for heat. The actual current boiler temperature is shown on the display.
- Turn both control knobs fully anticlockwise, then quickly turn the right hand knob 1/4 clockwise twice and back fully anticlockwise.
- The display will now alternate between ‘SF’ and the current boiler temperature and both green LEDs will flash.
- To set to maximum rate: Turn the left hand knob fully clockwise. The display will show ‘00’, indicating maximum rate, then revert to ‘P’ alternating with the current boiler temperature.
- To set to minimum rate: Turn the left hand knob fully anti-clockwise. When the display reads ‘0’ the boiler runs at minimum rate.
- This function is maintained for 20 minutes unless the maximum CH temperature is exceeded. The function can be disabled at any time by turning the right hand knob.
From manual 7647625 - 04, page 27.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% | 8.4% | 350 ppm |
CO₂ and CO from manual 7647625 - 04, page 40. Check against the data badge.
To assist the boiler to light prior to final setting, use a suitable hexagon key to wind out the Throttle Adjustment Screw until it is flush with the valve body, then turn the screw 4 full turns clockwise. (page 39)
Baxi Platinum Combi ErP 24 - 28 - 33 - 40
Covers: Platinum 24 Combi ErP, Platinum 28 Combi ErP, Platinum 33 Combi ErP, Platinum 40 Combi ErP
GC 47-077-04, 47-077-05, 47-077-06, 47-077-07
Entering Calibration / Service Mode (Max & Min Rate)
- Ensure that all external controls are calling for heat. The actual current boiler temperature is shown on the display.
- Turn both temperature control knobs fully anticlockwise, then quickly turn the right hand knob 1/4 clockwise twice and back fully anticlockwise (or DHW knob depending on section reference, both procedures specified in manual).
- The display will now alternate between 'SF' and the current boiler temperature and both green LEDs will flash.
- To set to maximum rate: Turn the left hand knob fully clockwise. The display will show '00' indicating maximum rate, then revert to 'P' alternating with the current boiler temperature.
- To set to minimum rate: Turn the left hand knob fully anticlockwise. When the display reads '0' the boiler runs at minimum rate.
- This function is maintained for 20 minutes unless the maximum CH temperature is exceeded.
- The function can be disabled at any time by turning the right hand knob (or DHW temperature knob).
From manual 7647627, page 29.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% | 8.4% | 350 ppm |
CO₂ and CO from manual 7647627, page 45. Check against the data badge.
IMPORTANT: After replacing the valve the CO2 must be checked and adjusted as detailed in Section 14.0 Setting the Gas Valve. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person - see section 12.1. (page 44)
Baxi Platinum Combi HE Range
Covers: Platinum 24 HE, Platinum 28 HE, Platinum 33 HE
GC 47-075-20, 47-075-21, 47-075-22
Entering Calibration Mode (Service / Max & Min Rate)
- Ensure that all external controls are calling for heat.
- Turn both temperature control knobs fully anticlockwise.
- Quickly turn the DHW temperature knob 1/4 clockwise twice and back fully anticlockwise.
- The display will now alternate between 'SF' and the current boiler temperature and both green LEDs will flash.
- Turn CH temperature control knob fully clockwise to indicate maximum rate ('00' then 'P' alternating with current boiler temperature).
- Turn the CH temperature control knob fully anticlockwise to run the boiler at minimum rate (display reads '0').
- The calibration function is active for 20 minutes unless the maximum CH temperature is exceeded, and can be disabled at any time by turning the DHW temperature knob.
From manual 5116280, page 30.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | – |
CO₂ and CO from manual 5116280, page 43. Check against the data badge.
The gas valve is factory set and the burner pressure cannot be measured as it is altered by suction of the fan and modulates as demand on the boiler alters. (page 30)
Baxi Platinum Compact Combi
Covers: PLATINUM COMPACT 25 COMBI, PLATINUM COMPACT 30 COMBI, PLATINUM COMPACT 36 COMBI
GC 47-077-71, 47-077-72, 47-077-73
Chimney Sweep / Calibration Mode (Combustion Check)
- Turn both control knobs fully anticlockwise and leave for 10 seconds.
- Turn the DHW knob 1/4 turn twice in quick succession (within 2 seconds).
- Display will show '304'.
- Turn the CH knob fully clockwise to set Maximum output ('100').
- Turn the CH knob fully anticlockwise to set Minimum output ('0').
- Exit mode by turning the DHW control knob clockwise.
From manual 7846425-01, page 52.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.0% (+0.3) | 8.5% (+0.1) | 350 ppm |
CO₂ and CO from manual 7846425-01, page 64. Check against the data badge.
The boiler is factory set for use on Natural Gas (G20). (page 19)
Baxi Platinum+ 40 Combi
Covers: Platinum+ 40 Combi
GC 47-077-41
Entering Calibration / Service Mode (Max & Min Rate)
- Ensure that all external controls are calling for heat. The actual current boiler temperature is shown on the display.
- Turn both control knobs fully anticlockwise, then quickly turn the right hand knob 1/4 clockwise twice and back fully anticlockwise.
- The display will now alternate between 'SF' and the current boiler temperature and both green LEDs will flash.
- To set to maximum rate: Turn the left hand knob fully clockwise. As the knob is turned the display will change, indicating the fan speed. The display will show '00', indicating maximum rate, then revert to 'P' alternating with the current boiler temperature.
- To set to minimum rate: Turn the left hand knob fully anti-clockwise. As the knob is turned the display will change, indicating the fan speed. When the display reads ' 0' the boiler runs at minimum rate.
- This function is maintained for 20 minutes unless the maximum CH temperature is exceeded. The function can be disabled at any time by turning the right hand knob.
From manual 7734477-01, page 30.
IMPORTANT: After replacing the valve the CO2 must be checked and adjusted as detailed in Section 14.0 Setting the Gas Valve. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person. (page 44)
Baxi Solo 2 PF
Covers: Solo 2 60 PF
GC 41-077-74
Entering Service Mode / Commissioning Ignition
- Turn the boiler thermostat control knob fully anti-clockwise to the OFF position marked 0.
- Ensure that the electricity supply is turned ON and set any external controls to the ON position.
- Turn the boiler thermostat knob fully clockwise.
- The fan will start running and after approximately 5 seconds, the ignition spark will commence.
- The sparking will continue until the pilot light is established and then the main burner will light from the pilot flame.
From manual Comp No 230988, page 31.
Baxi Solo 2 RS Range Wall Mounted Room Sealed Gas Fired Central Heating Boilers
Covers: Solo 2 50 RS
GC 41-077-78
Enter Service Mode / Dismantling the Boiler
- Isolate the electrical supply to the boiler.
- Remove lower door panel.
- Take out the two screws and washers, draw outer case forward and clear of the boiler.
- Turn off gas supply at the service tap and disconnect the union.
- Disconnect the electrical plug on the gas valve by removing screw and pulling forward.
- Disconnect the two wires from the overheat thermostat.
- Loosen the screw on the capillary retaining washer, release capillaries and remove phials from the thermostat pocket.
- Remove brass sealing plug with fibre washer.
- Loosen the six screws sufficiently for the removal of the combustion chamber door and remove door complete with burner.
From manual Comp No 232184, page 30.
Each appliance is preset at its MAXIMUM heat input rating (page )
Baxi Solo 3 PF Wall Mounted Powered Flue Gas Fired Central Heating Unit
Covers: Solo PF 3 40
GC 41-075-05
Commissioning / Operating the Boiler (Force Burner On)
- Ensure that the electrical supply is isolated.
- Turn the gas service cock anti-clockwise to the ON position and check for gas soundness up to the gas valve.
- Loosen the pressure test point screw on the right hand side of the gas control valve and connect a pressure gauge.
- Turn the boiler thermostat control knob fully anti-clockwise to the OFF position marked 0.
- Ensure that the electricity supply is turned ON and set any external controls to the ON position.
- Turn the boiler thermostat knob fully clockwise.
- The fan will start running and after approximately 10 seconds, the ignition spark will commence.
- The sparking will continue until the pilot light is established and then the main burner will light from the pilot flame.
From manual Comp No 244096, page 32.
Baxi Solo 30/4 RS, 40/4 RS, 50/4 RS, 60/4 RS
Covers: Solo 40/4 RS
GC 41-077-48
Adjusting Burner Pressure (Service / Commissioning)
- Light main burner by turning thermostat knob to high setting.
- Remove cover screw to adjust governor.
- Check pressure after 10 minutes. Adjust if necessary to the relevant figures for the corresponding model.
- Turn boiler thermostat knob to the OFF position marked O.
- Refit burner pressure test point screw and governor cover screw.
- Turn boiler thermostat knob to required setting.
- Make final check for gas soundness of all gas-carrying joints on boiler.
From the installation and servicing manual, page 25.
Baxi Solo HE A Range Wall Mounted Powered Flue Condensing Boilers Gas Fired Central Heating Units
Covers: Solo 12 HE A, Solo 15 HE A, Solo 18 HE A, Solo 24 HE A, Solo 30 HE A
GC 41-075-65, 41-075-66, 41-075-67, 41-075-68, 41-075-69
Operating at Maximum Rate for Combustion Check
- Ensure all external controls are calling for heat.
- Ensure the system is cold.
- Turn the boiler control knob fully clockwise.
- Allow the combustion to stabilise.
- Insert analyser probe into the flue gas test point.
From manual 7204218 - 06, page 39.
Operating at Low Rate for Combustion Check
- Set boiler to operate at a low rate.
- If not possible to adjust using boiler controls, set system such that boiler modulates to as low an input as possible without burner extinguishing (e.g. by closing radiator valves).
- Allow combustion to stabilise.
- Do not insert probe to avoid 'flooding' the analyser.
From manual 7204218 - 06, page 39.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.0% ± 1% | – | – |
CO₂ and CO from manual 7204218 - 06, page 6. Check against the data badge.
IMPORTANT: The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. No measurement of the combustion is necessary. Do not adjust the air/gas ratio valve. (page 38)
IMPORTANT: No adjustment of the gas valve is permissible. (page 44)
Baxi System HE Range Gas Fired Wall Mounted Condensing Boiler
Covers: Megaflo System 15 HE, Megaflo System 15 HE A, Megaflo System 18 HE, Megaflo System 18 HE A, Megaflo System 24 HE A, Megaflo System 28 HE A, Megaflo System 32 HE, Megaflo System 32 HE A
GC 41-075-52, 41-075-53, 41-075-54, 41-075-55, 41-075-56, 41-075-57, 41-075-58, 41-075-59, 47-075-61, 47-075-63
Enter Calibration/Service Mode (for Gas Rate and CO2 checks)
- Ensure that all external controls are calling for heat.
- Turn both temperature control knobs fully anticlockwise.
- Quickly turn the Calibration Control knob 1/4 clockwise twice and back fully anticlockwise.
- The display will now alternate between 'SF' and the current boiler temperature and both green LEDs will flash.
- Turn CH temperature control knob fully clockwise to reach maximum rate ('00' displayed, then 'P' alternating with current boiler temperature).
From the installation and servicing manual, page 33.
Force Minimum Rate in Calibration/Service Mode
- With the calibration function active, turn the CH temperature knob fully anticlockwise.
- When the display reads '0' the boiler runs at minimum rate.
From the installation and servicing manual, page 45.
Exit Calibration/Service Mode
- The Calibration Function is maintained for 20 minutes unless the maximum CH temperature is exceeded.
- The function can be disabled at any time by turning the Calibration Control knob.
From the installation and servicing manual, page 33.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | – |
CO₂ and CO from the installation and servicing manual, page 35. Check against the data badge.
The gas valve is factory set and the burner pressure cannot be measured as it is altered by suction of the fan and modulates as demand on the boiler alters. (page 33)
Duo-tec 2 Combi GA Range
Covers: Duo-tec 2 Combi 33 GA, Duo-tec 2 Combi 40 GA
GC 47-075-56, 47-075-57
Enter Chimney Sweep Function (Maximum and Minimum Rate)
- Press the i P button and the + button together and hold for at least 6 seconds.
- 'On' will be displayed briefly, followed by '304' then the boiler output expressed as percentage i.e. '100'.
- Press the - button until '00' is displayed, indicating minimum input.
From manual 7206334 - 09 (9/14), page 28.
Exit Chimney Sweep Function
- To exit the function press i P & IIII°+ together for 6 seconds.
From manual 7206334 - 09 (9/14), page 28.
Activate Calibration Function
- The function is activated by pressing buttons |||| - and (power/reset R symbol) together for 6 seconds then quickly pressing button i P while 'On' is displayed.
- The Ignition Phase fan speed code will then be displayed. Calibration will take approximately 5 minutes.
From manual 7206334 - 09 (9/14), page 42.
| Model | Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|---|
| Duo-tec 2 Combi 33 GA | Natural gas | 9.0% ± 0.7 | – | 350 ppm |
| Duo-tec 2 Combi 33 GA | LPG | 10.5% ± 1.0 | – | 350 ppm |
| Duo-tec 2 Combi 40 GA | Natural gas | 9.0% ± 0.7 | 9.0% ± 0.7 | 350 ppm |
| Duo-tec 2 Combi 40 GA | LPG | 10.5% ± 1.0 | 10.5% ± 1.0 | 350 ppm |
CO₂ and CO from manual 7206334 - 09 (9/14), page 24, 42. Check against the data badge.
The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. No measurement of the combustion is necessary. Do not adjust the air/gas ratio valve. (page 27)
Duo-tec Combi HE A Range Gas Fired Wall Mounted Condensing Combination Boiler
Covers: Duo-tec Combi 28 HE A, Duo-tec Combi 33 HE A, Duo-tec Combi 40 HE A
GC 47-075-36, 47-075-37, 47-075-38
Enter Calibration Mode / Force Max & Min Rate
- Ensure that the integral timer and any external controls are calling for heat, and the selector switch is in the central heating and hot water position.
- Turn both temperature control knobs fully anticlockwise, then quickly turn the DHW temperature knob 1/4 clockwise twice and back fully anticlockwise.
- The display will now alternate between 'SF' and the current boiler temperature and both green LEDs will flash.
- To force maximum rate: Turn CH temperature control knob fully clockwise. The display will change from '0' to '00' indicating maximum rate, then revert to 'P' alternating with the current boiler temperature.
- To force minimum rate: Turn the CH temperature knob fully anti-clockwise. When the display reads '0' the boiler runs at minimum rate.
- The 'Calibration Function' is active for 20 minutes unless the maximum CH temperature is exceeded.
- The function can be disabled at any time by turning the DHW temperature knob.
From the installation and servicing manual, page 34.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | – |
CO₂ and CO from the installation and servicing manual, page 36. Check against the data badge.
The gas valve is factory set and the burner pressure cannot be measured as it is altered by suction of the fan and modulates as demand on the boiler alters. (page 34)
EcoBlue Advance Combi
Covers: EcoBlue Advance 24 Combi ErPD, EcoBlue Advance 28 Combi ErPD, EcoBlue Advance 33 Combi ErPD, EcoBlue Advance 40 Combi ErPD
GC 47-077-14, 47-077-15, 47-077-16, 47-077-17
Enter Chimney Sweep Mode (Check Combustion)
- Press the R button & the IIII'- button together and hold for at least 6 seconds.
- 0n is displayed briefly followed by 303 and the current setting point (1, 2 or 3) flashing alternately.
- Press the IIII'- or IIII'+ button and the current setting point will flash (1, 2 or 3); press the IIII'- or IIII'+ button again to alter the boiler input setting (3 = MAX. HEATING input, 2 = MAX. DHW input, 1 = MIN. input).
- The combustion (CO level & CO/CO2 ratio) must be measured and recorded at MAXIMUM DHW input & MINIMUM input.
- Press the R button & the IIII'- button together again for at least 6 seconds to exit.
From manual 7219715 - 03, page 44.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | 350 ppm |
CO₂ and CO from manual 7219715 - 03, page 63. Check against the data badge.
After replacing the valve the CO2 must be checked and adjusted as detailed in Section 10.3.25 Setting the Gas Valve. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person - see section 10.1.3. (page 62)
EcoBlue Advance Heat
Covers: EcoBlue Advance 13 Heat ErP, EcoBlue Advance 16 Heat ErP, EcoBlue Advance 19 Heat ErP, EcoBlue Advance 21 Heat ErP, EcoBlue Advance 25 Heat ErP, EcoBlue Advance 30 Heat ErP
GC 41-470-34, 41-470-35, 41-470-36, 41-470-37, 41-470-38, 41-470-55
Enter Chimney Sweep Mode (CSM)
- Press the Chimney Sweep button for 3 seconds.
- CSM is activated and will go to the min rate.
- Pressing again will make it adjust to max rate.
- To exit press the RESET for 3 seconds.
From manual 7684198-01, page 43.
Force Max & Min Rate
- Press the Chimney Sweep button for approximately 3 seconds to select minimum rate (status signal is orange and flashes green briefly).
- Press the Chimney Sweep button again once to select maximum rate.
From manual 7684198-01, page 55.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.3% ± 0.1% | 8.9% ± 0.1% | 350 ppm |
CO₂ and CO from manual 7684198-01, page 55. Check against the data badge.
The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. (page 42)
EcoBlue Heat (manual 7212435 - 02)
Covers: EcoBlue Heat
GC 41-470-02, 41-470-03, 41-470-04, 41-470-05, 41-470-06
Chimney Sweep Mode Activation
- Press the chimney-sweep button for 3 seconds.
- CSM is activated and will go to the min rate.
- Pressing again will make it adjust to max rate.
- To exit press the RESET for 3 seconds.
From manual 7212435 - 02, page 41.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.3% ± 0.1% | 8.9% ± 0.1% | 350 ppm |
CO₂ and CO from manual 7212435 - 02, page 55. Check against the data badge.
The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. (page 40)
EcoBlue Heat (manual 7684226-01)
Covers: EcoBlue 12 Heat ErP, EcoBlue 15 Heat ErP, EcoBlue 18 Heat ErP, EcoBlue 21 Heat ErP, EcoBlue 24 Heat ErP
GC 41-470-29, 41-470-30, 41-470-31, 41-470-32, 41-470-33
Chimney Sweep Mode Activation
- Press the [chimney] button for 3 seconds.
- CSM is activated and will go to the min rate.
- Pressing again will make it adjust to max rate.
- To exit press the RESET for 3 seconds.
From manual 7684226-01, page 42.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.3% ± 0.1% | 8.9% ± 0.1% | 350 ppm |
CO₂ and CO from manual 7684226-01, page 54. Check against the data badge.
The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. (page 41)
EcoBlue System (manual 7212140)
Covers: Ecoblue 12 System, Ecoblue 15 System, Ecoblue 18 System, Ecoblue 24 System, Ecoblue 28 System, Ecoblue 32 System
GC 41-077-95, 41-077-96, 41-077-97, 41-077-98, 41-077-99, 41-470-01
Enter Chimney Sweep Mode (Check Combustion / Force Max & Min Rate)
- Press the standby/reset (⏻/R) button and the radiator − (CH −) button together and hold for at least 6 seconds. On is displayed briefly followed by 303 and the current setting point (eg. 1, 2 or 3 ) flashing alternately.
- To adjust the boiler input setting, press the radiator − (CH −) or radiator + (CH +) button and the current setting point will flash (eg. 1, 2 or 3 ). Press the ||||- or ||||+ button again to alter the boiler input setting.
- The combustion (CO level & CO/CO2 ratio) must be measured and recorded at MAXIMUM DHW input & MINIMUM input.
- Follow the flow chart on the next page to comply with the requirement to check combustion on commissioning.
- Press the standby/reset (⏻/R) button and the radiator − (CH −) button again for at least 6 seconds to exit.
- Press the standby/reset (⏻/R) button once to bring the boiler out of 'Standby' mode.
- Use the tap/radiator button to toggle between the CH (radiator symbol) and DHW (tap symbol) settings to activate the required modes.
From manual 7212140, page 45.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | – |
CO₂ and CO from manual 7212140, page 63. Check against the data badge.
After replacing the valve the CO2 must be checked and adjusted as detailed in Section 10.3.20 Setting the Gas Valve. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person - see section 10.1.3. (page 62)
EcoBlue System (manual 7219708 - 03)
Covers: EcoBlue System
GC 41-070-23, 41-070-24, 41-070-25, 41-070-26, 41-070-27, 41-470-28
Enter Chimney Sweep Mode (Check Combustion / Gas Settings)
- Ensure the system is cold and the gas supply is turned on and purged.
- Press the R button and the IIII'- button together and hold for at least 6 seconds; 'On' is briefly displayed followed by '303' and the current setting point (1, 2 or 3) flashing alternately.
- Press the IIII'- or IIII'+ button so the current setting point flashes (eg. 1, 2 or 3).
- Press the IIII'- or IIII'+ button again to alter the boiler input setting (3 = MAX heating input, 2 = MAX DHW input, 1 = MIN input).
- Measure and record combustion (CO level and CO/CO2 ratio) at MAXIMUM DHW input and MINIMUM input.
- Press the R button and the IIII'- button together again for at least 6 seconds to exit.
- Press the R button once to bring the boiler out of 'Standby' mode.
- Use the CH/DHW button to toggle through the CH and DHW settings to activate the required modes.
From manual 7219708 - 03, page 45.
After replacing the valve the CO2 must be checked and adjusted as detailed in Section 10.3.20 Setting the Gas Valve. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person (page 62)
EcoBlue System Gas Fired Wall Mounted Condensing System Boiler
Covers: Ecoblue 28 System ErP, Ecoblue18 System ErP
GC 41-470-25, 41-470-27
Enter Chimney Sweep Mode / Service Mode
- Press the ⏻R button & the ||||'- button together and hold for at least 6 seconds. 'On' is displayed briefly followed by '303' and the current setting point (1, 2 or 3) flashing alternately.
- To adjust the boiler input setting, press the ||||'- or ||||'+ button and the current setting point will flash (1, 2 or 3).
- Press the ||||'- or ||||'+ button again to alter the boiler input setting (3 = MAX. HEATING input, 2 = MAX. DHW input, 1 = MIN. input).
- Press the ⏻R button & the ||||'- button together again for at least 6 seconds to exit.
From manual 7219708, page 45.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | – |
CO₂ and CO from manual 7219708, page 63. Check against the data badge.
Luna 3 Comfort
Covers: Luna 3 Comfort
Electronic Calibration (Board Jumper Settings)
- T.RISC: 30-85°C (OFF) vs 30-45°C (ON)
- GPL: Natural Gas (OFF) vs LPG (ON)
- T-off: 3-minute standby (OFF) vs 10-second standby (ON)
- POMPA: 3-min post-circulation (OFF) vs continuous pump (ON)
From manual 921.933.2, page 27.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 7% | 7% | – |
| LPG | 8.5% | 8.5% | – |
CO₂ and CO from manual 921.933.2, page 15. Check against the data badge.
The burner pressure settings have been factory set and do not require adjusting. (page 23)
Neta-tec Combi GA Range
Covers: Neta-tec Combi 24 GA, Neta-tec Combi 28 GA, Neta-tec Combi 33 GA
GC 47-075-51, 47-075-52, 47-075-53
Enter / Exit Chimney Sweep Function (Maximum & Minimum Rate)
- Press the 'i P' button & the 'IIII +' button together and hold for at least 6 seconds.
- 'On' will be displayed briefly, followed by '304' then '100' when the boiler is lit, indicating the CH output is at MAXIMUM ('Chimney Sweep Function').
- Press the 'i P' button & the 'IIII +' button together and hold for at least 6 seconds to exit the function.
From the installation and servicing manual, page 29.
Calibration Function
- IMPORTANT: Do not commence the Calibration Function whilst the burner is lit! The case front panel MUST be fitted.
- The function is activated by pressing the '-' button and the R (reset) button together for 6 seconds, then quickly pressing the 'iP' button while 'On' is displayed. The Ignition Phase fan speed code will then be displayed. Calibration will take approximately 5 minutes.
- If '303' is displayed, then the Calibration Function has not been activated correctly. Isolate and reinstate all power sources to the boiler and repeat the above.
- The boiler will automatically calibrate at '100', the Ignition Phase speed, then '00'. These represent the percentage of MAXIMUM fan speed (i.e. '00' is MINIMUM fan speed). Once the boiler has stabilised and self-calibrated at each fan speed, the P and flame symbols will be displayed before the next speed is automatically set.
- When self-calibration is complete the boiler will run at MINIMUM fan speed ('00' displayed). The following symbols will also be displayed: droplet, tap, and IIII flashing together at regular intervals.
- To exit the function press R. 'ESC' will be displayed and the calibration function completed.
From the installation and servicing manual, page 42.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 9.0% ± 0.7 | – | – |
| LPG | 10.5% ± 1.0 | – | – |
CO₂ and CO from the installation and servicing manual, page 10. Check against the data badge.
IMPORTANT: The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. No measurement of the combustion is necessary. Do not adjust the air/gas ratio valve. (page 27)
Platinum Combi HE A Range
Covers: Platinum Combi 24 HE, Platinum Combi 24 HE A, Platinum Combi 28 HE, Platinum Combi 28 HE A, Platinum Combi 33 HE, Platinum Combi 33 HE A, Platinum Combi 40 HE, Platinum Combi 40 HE A
GC 47-075-27, 47-075-28, 47-075-29, 47-075-30, 47-075-31, 47-075-32, 47-075-33, 47-075-34
Enter Calibration (Service) Mode & Force Max/Min Rate
- Ensure that all external controls are calling for heat, and the selector switch is in the central heating and hot water position.
- Turn both temperature control knobs fully anticlockwise, then quickly turn the DHW (right-hand) temperature knob 1/4 clockwise twice and back fully anticlockwise.
- The display will alternate between 'SF' and the current boiler temperature and both green LEDs will flash.
- To force Maximum Rate: Turn the CH (left-hand) temperature control knob fully clockwise. The display will show '00', indicating maximum rate, then revert to 'P' alternating with the current boiler temperature.
- To force Minimum Rate: Turn the CH (left-hand) temperature control knob fully anti-clockwise. When the display reads '0', the boiler runs at minimum rate.
- The calibration function is active for 20 minutes unless maximum CH temperature is exceeded.
- The function can be disabled at any time by turning the DHW temperature control knob.
From manual 5121651, page 35.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% ± 0.2 | 8.4% ± 0.2 | – |
CO₂ and CO from manual 5121651, page 48. Check against the data badge.
IMPORTANT: The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. No measurement of the combustion is necessary. Do not adjust the air/gas ratio valve. (page 33)
Platinum Heat (System) / Platinum+ 32 System
Covers: Platinum Heat
GC 41-470-95
Enter Service/Calibration Mode
- Ensure controls are calling for heat.
- Turn both temperature control knobs fully anticlockwise.
- Quickly turn the Calibration Control (right hand) knob 1/4 clockwise twice.
- Turn Calibration Control knob back fully anticlockwise.
- Display will alternate between 'SF' and current temperature; green LEDs flash.
From manual 7753842-01, page 27.
Force Max/Min Rate
- Set to Max: Turn left hand CH knob fully clockwise (Display shows '00' then 'P').
- Set to Min: Turn left hand CH knob fully anticlockwise (Display shows '0').
From manual 7753842-01, page 27.
| Gas | CO₂ max rate | CO₂ min rate | CO max |
|---|---|---|---|
| Natural gas | 8.7% | 8.4% | 350 ppm |
CO₂ and CO from manual 7753842-01, page 40. Check against the data badge.
Suprima 30 - 80 Wall Mounted Fan Assisted Balanced Flue Gas Boilers
Covers: Suprima 60
GC 41-607-78
To enter service / operating check state
- Set the boiler temperature control knob to 'O' Standby.
- Turn the boiler gas service cock to the 'On' position and ensure main gas supply is 'On'.
- Ensure system is full of water and pump/radiator isolating valves are open.
- Ensure main electricity supply is 'On'.
- Set time control to 'On' and room/cylinder thermostats to high temperatures.
- Set the temperature control knob to its maximum setting to fire the boiler.
From manual 559767, page 22.
The commissioning and boiler adjustment must only be carried out by a suitably qualified personnel. (page )
Nothing matches that. The app covers more Baxi models than have a service-mode procedure here.
The app
Every Baxi manual, searchable on the job
Service mode, gas valve and combustion figures, fault codes and the full manual for the boiler in front of you, plus Ask Flint for anything the manual covers.
Start 7 days freeThen £3.99 a month or £29.99 a year. Cancel any time.
Common questions
Is service mode the same as chimney sweep mode?
Yes, in practice. Makers use different names for the same function: service mode, chimney sweep mode, test mode, calibration mode, check programme. Each one holds the burner at a fixed rate, usually maximum then minimum, so you can take a stable combustion reading.
Can I adjust the gas valve while it's in service mode?
Only where the manual gives an adjustment procedure, and only with an analyser in the flue. Many current boilers are set at the factory and the manual says not to touch the gas valve. Where a manual says that, it is shown with the procedure above.
Other makers
AlphaAristonAtagBiasiChaffoteauxFerroliGlow-wormHalsteadHeatlineIdealIntergasJohnson StarleyKestonMainPottertonRemehaSimeVaillantViessmannVokeraWorcester Bosch
Service mode and combustion checks are work for a competent, Gas Safe registered engineer. These procedures are taken from the manufacturers' manuals and inform your judgement; they don't replace it. Always work to the manual for the exact appliance, its data badge and the current standards.